{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19689","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19689","canonicalUrl":"https://aoctrl.com/schneider/A9N19689","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19689","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN N Vigi, Type AC RCBO, 40 A, 300 mA, 6 kA, 1P+N, C-curve, DIN rail.","salesMarkdown":"It protects a single outgoing circuit against overload, short-circuit, and earth faults, with the residual-current element integrated into the same compact body. Rated 40 A at 30 °C with a C-curve magnetic trip (5...10 x In), it breaks up to 6000 A at 230 V AC (Icn per EN 61009). The earth-leakage side is Type AC, 300 mA sensitivity, voltage-independent, instantaneous trip — no time delay. Terminals are tunnel type, rated for one cable: up to 10 mm² flexible or 16 mm² rigid. The toggle gives ON/OFF indication and local signalling — no auxiliary contact built in, so if you need remote status, plan for a separate auxiliary switch module alongside it.","metaTitle":"Schneider Electric A9N19689 DPN N Vigi RCBO, 40 A, 30 mA, Ty","metaDescription":"Schneider Electric A9N19689 DPN N Vigi RCBO, 40 A rated current, 300 mA earth-leakage sensitivity, Type AC, 6 kA breaking capacity. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type AC","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-2-1 EN/IEC 61009-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"40 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aed3684b971460e38a2db56819fdfb7b.pdf","sourceUrl":"https://www.se.com/in/en/product/A9N19689/acti-9-earth-leakage-circuit-breaker-dpn-n-vigi-1p-+-n-40a-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19689/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N19689?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is A9N19689's listed type (Type AC) on this component line?","answer":"The earth-leakage detection type is Type AC, meaning it responds to sinusoidal AC residual currents only — not pulsed DC or high-frequency signals."},{"question":"What is A9N19689's listed range (Acti9) on this component line?","answer":"It belongs to the Schneider Electric Acti9 range, a modular DIN-rail system for residential and commercial distribution boards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19689","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19689 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}