{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19760","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19760","canonicalUrl":"https://aoctrl.com/schneider/A9N19760","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19760","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi RCBO, 1P+N, 40 A, B curve, 6 kA breaking capacity, integrated earth-leakage protection, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N19760 is an Acti9 DPN Vigi RCBO — a combined overcurrent and residual-current device in a single 36 mm-wide module. It protects a single-phase final subcircuit against overload, short-circuit (B-curve magnetic trip at 3 to 5 × In), and earth leakage, all in one clip-on DIN-rail unit. Rated 40 A with a 6 kA breaking capacity at 230 V AC, it is sized for residential or light commercial distribution boards where space is tight and you want one device instead of a separate MCB and RCCB. The 40 A rated current (In) sets the continuous load ceiling — size the downstream cable and load for that, not above. The B-curve characteristic means the magnetic trip fires between 3 and 5 times In (120 to 200 A), so it suits resistive and general-purpose loads with modest inrush; avoid it on motor or transformer circuits that need a C or D curve. The 6 kA Icn at 230 V AC is the short-circuit breaking capacity per EN/IEC 61009-2-1 — adequate for most domestic and small commercial boards, but verify the prospective fault current at the point of installation. Integrated earth-leakage protection means no separate RCCB needed; the device occupies 4 × 9 mm pitches (36 mm) on the DIN rail, leaving room for other modules in the enclosure. Clip-on mounting to a standard DIN rail, tunnel terminals accepting 0.75 to 16 mm² rigid or 0.33 to 10 mm² flexible, and a tightening torque of 2 N·m.","metaTitle":"Schneider Electric A9N19760 Acti9 DPN Vigi RCBO, 40 A, B Cur","metaDescription":"Schneider Electric A9N19760 Acti9 DPN Vigi RCBO. 40 A rated current, B curve, 6 kA breaking capacity, integrated earth-leakage protection. Clip-on DIN rail mount. Active production","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DPN Vigi","Mounting mode":"Clip-on","Surge current":"250 A","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to EN/IEC 61009-2-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"6000 A Icn at 220...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Device short name":"DPN N Vigi","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"90 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"III conforming to IEC 60364","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Sealable Padlocking device","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-30...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 220...240 V AC 50/60 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3cc1cd00e7284678cd40cdb56b3e4587.pdf","sourceUrl":"https://www.se.com/in/en/product/A9N19760/acti9-dpn-n-vigi-rcbo-1p+n-40a-b-curve-6000a-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19760/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N19760?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; we source the A9N19760 through independent distribution and quote to order."},{"question":"What is the breaking capacity of the A9N19760?","answer":"The A9N19760 has a 6 kA Icn breaking capacity at 220–240 V AC, 50/60 Hz, per EN/IEC 61009-2-1."},{"question":"What is the closest alternative to the A9N19760?","answer":"Within the Acti9 range, the A9N19760 is a 1P+N DPN Vigi RCBO at 40 A B-curve. A direct sibling would be the same device with a different current rating or curve — no pin-compatible drop-in exists outside the DPN Vigi family. For a parametric match, compare the rated current, curve, and breaking capacity to your load requirements."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19760","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19760 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}