{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19874","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19874","canonicalUrl":"https://aoctrl.com/schneider/A9N19874","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19874","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DCP Vigi, RCBO, 3P, 16 A, C-curve, 30 mA earth leakage, 10 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric A9N19874 is an Acti9 DCP Vigi residual current breaker with overcurrent protection (RCBO) — a single module that combines a 16 A thermal-magnetic MCB with integrated 30 mA earth-leakage protection in a 3-pole package. Rated breaking capacity is 10 kA Icu at 220...240 V AC per EN/IEC 60947-2, with an Icn of 6000 A per EN/IEC 61009-1 — enough for most distribution sub-panels in commercial and light industrial installations. Tunnel terminals accept 1...35 mm² rigid or 1...25 mm² flexible on top or bottom; strip length 12 mm, tighten to 2 N·m. Local signalling shows ON, OFF, and fault trip via the toggle position.","metaTitle":"Schneider Electric A9N19874 Acti9 DCP Vigi RCBO, 16 A, 30 mA","metaDescription":"Schneider Electric A9N19874 Acti9 DCP Vigi RCBO, 16 A rated current, 30 mA earth leakage, C-curve, 10 kA breaking capacity, 3P, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"76 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DCP Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"2","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2 6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-1","Device short name":"DCP N Vigi","Network frequency":"50 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA","Number of protected poles":"3","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Non padlockable","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"7.5 kA 75 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2 6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/791bbc0d6745c42de3cab371d771b3be.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19874/acti9-dcp-n-vigi-rcbo-3p-16a-c-curve-6000a-10ka-30ma-type-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19874/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N19874?","answer":"10 kA Icu at 220...240 V AC per EN/IEC 60947-2, and 6000 A Icn per EN/IEC 61009-1."},{"question":"What earth-leakage sensitivity does this RCBO have?","answer":"Integrated 30 mA earth-leakage protection, which covers personnel protection requirements in most distribution circuits."},{"question":"Where can I buy the A9N19874?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What standards does A9N19874 comply with?","answer":"EN/IEC 61009-2-1 for RCBOs, and EN/IEC 60947-2 for the breaking capacity rating. Overvoltage category III, suitable for distribution panels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19874","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19874 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}