{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19897","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19897","canonicalUrl":"https://aoctrl.com/schneider/A9N19897","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19897","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DCP Vigi, RCBO, 2P, 32 A, B curve, 30 mA earth leakage, 10 kA Icn, DIN rail mount.","salesMarkdown":"The Schneider Electric A9N19897 is a 2-pole Acti9 DCP Vigi residual current breaker with overcurrent protection (RCBO) rated at 32 A with a B tripping curve and integrated 30 mA earth-leakage protection — one unit covers both overcurrent and ground-fault on a single DIN-rail module. Breaking capacity is 10 kA Icn / Icu at 220...240 V AC 50 Hz per EN/IEC 61009-2-1 and EN/IEC 60947-2, so it clears a fault up to 10 kA without welding the contacts or cascading upstream. Clip-on mount on standard DIN rail; 36 mm width (4 × 9 mm pitches) fits a 2-module slot in a consumer unit or distribution board. Tunnel terminals accept 1–35 mm² rigid or 1–25 mm² flexible; strip length 12 mm, tighten to 2 N·m top or bottom. Designed and tested to EN/IEC 61009-2-1 and EN/IEC 60947-2, overvoltage category III, IP20 (IP40 in modular enclosure), tropicalisation class 2.","metaTitle":"Schneider Electric A9N19897 Acti9 DCP Vigi RCBO, 32 A B Curv","metaDescription":"Schneider Electric A9N19897 Acti9 DCP Vigi RCBO, 2P, 32 A, B curve, 30 mA earth leakage, 10 kA breaking capacity. Current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"76 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 61009-2-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 DCP Vigi","Mounting mode":"Clip-on","Tropicalisation":"2","lifecycle_stage":"current","Limitation class":"2","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Breaking capacity":"10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 10 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","Device short name":"DCP H Vigi","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"12 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Earth-leakage sensitivity":"30 mA","Number of protected poles":"2","Product or component type":"Residual current breaker with overcurrent protection (RCBO)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Non padlockable","Electromagnetic compatibility":"8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"220...240 V AC 50 Hz","Rated breaking and making capacity":"Idm 4500 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...40 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 7.5 kA 75 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cbe911ca5a7ff9143f54b5f5d96ef16a.pdf","sourceUrl":"https://www.se.com/be/en/product/A9N19897/acti9-dcp-h-vigi-rcbo-2p-32a-b-curve-10000a-10ka-30ma-type-asi/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19897/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the A9N19897?","answer":"32 A rated current, B curve (3–5× In magnetic trip), 30 mA earth-leakage sensitivity, 10 kA breaking capacity at 220–240 V AC, 2 poles, thermal-magnetic trip."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19897","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19897 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}