{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P01CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P01CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P01CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P01CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P01CGN, 1 A rated current, curve C, 1 pole, 10 kA breaking capacity at 240 V AC, clip-on 35 mm DIN rail mounting.","salesMarkdown":"The Schneider Electric A9N1P01CGN is a 1 A miniature circuit breaker from the Acti9 xC60 series, single-pole, curve C, designed for AC distribution networks. It clips onto a 35 mm DIN rail and occupies two 9 mm pitches (18 mm wide). The 10 kA Icn breaking capacity at 240 V AC per IS/IEC 60898-1 means it can safely interrupt fault currents up to that level on a residential or light commercial final subcircuit — adequate for most domestic lighting and socket-outlet protection in regions following IEC 60898-1. ## Curve C and trip characteristics Curve C means the magnetic trip operates at 5 to 10 times In (5–10 A for this 1 A unit). That suits loads with moderate inrush — think lighting banks, small transformers, or general-purpose socket outlets. The thermal-magnetic trip element handles overloads; the magnetic coil clears short-circuits. For a 1 A breaker, the 5–10× In band gives a good balance between nuisance ride-through and fast fault clearance on typical final circuits. The 18 mm width (two 9 mm pitches) fits standard modular enclosures. Tunnel-type terminals at bottom accept up to 25 mm² rigid or 16 mm² flexible cable; strip length 13 mm. Tightening torque 2 N·m.","metaTitle":"Schneider Electric A9N1P01CGN Acti9 xC60 MCB, 1A Curve C, 1P","metaDescription":"Schneider Electric A9N1P01CGN Acti9 xC60 miniature circuit breaker, 1 A, curve C, 1 pole, 10 kA breaking capacity at 240 V AC, IS/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P01CGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-1a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P01CGN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9N1P01CGN?","answer":"It has a 10 kA Icn breaking capacity at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1."},{"question":"What is the closest alternative to the A9N1P01CGN in the same family?","answer":"Within the Acti9 xC60 series, the same 1 A curve C 1P breaker carries the same footprint and ratings; no pin-compatible alternative exists because the mounting and terminal layout are identical across the series."},{"question":"What compliance documentation does Schneider provide for the A9N1P01CGN?","answer":"The breaker complies with IS/IEC 60898-1 and includes tropicalisation per IEC 60068-1 (class 2). Pollution degree 3, overvoltage category IV. The manufacturer provides a declaration of conformity and test certificates on request."},{"question":"Where can I buy the A9N1P01CGN and how is it quoted?","answer":"The A9N1P01CGN is sourced to order through independent distribution. Submit an RFQ for current availability and pricing; volume quotations are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P01CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P01CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}