{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P03CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P03CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P03CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P03CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, A9N1P03CGN, miniature circuit breaker, 1P, 3 A, C-curve, 10 kA Icn at 240 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N1P03CGN is an Acti9 xC60 miniature circuit breaker — a 1-pole, 3 A thermal-magnetic MCB with a C-curve (magnetic tripping between 5 and 10 times In). Rated breaking capacity is 10 kA Icn at 240 V AC, 50/60 Hz, per IS/IEC 60898-1. That's the standard domestic and light commercial short-circuit rating for this class — adequate for most final distribution boards where the upstream device limits prospective fault current. The C-curve means it holds magnetic trips for inrush-heavy loads (small motors, transformers, lighting ballasts) while still clearing fast on hard shorts. Depth is 77.5 mm, height 85 mm. Overvoltage category IV (suitable for main incoming panels). Pollution degree 3 (condensation and conductive pollution allowed). Tightening torque 2 N·m.","metaTitle":"Schneider Electric A9N1P03CGN Acti9 xC60 MCB, 3 A C-Curve 1P","metaDescription":"Schneider Electric A9N1P03CGN Acti9 xC60 miniature circuit breaker, 3 A rated current, C-curve, 1-pole, 10 kA breaking capacity at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"3 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P03CGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-3a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P03CGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N1P03CGN and how do I get a price?","answer":"The A9N1P03CGN is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing."},{"question":"What is A9N1P03CGN's breaking capacity?","answer":"The A9N1P03CGN has a rated breaking capacity of 10 kA Icn at 240 V AC, 50/60 Hz, conforming to IS/IEC 60898-1."},{"question":"What is the C-curve on this MCB?","answer":"The C-curve means magnetic tripping occurs between 5 and 10 times the rated current (In), so for the 3 A version, magnetic trip is between 15 A and 30 A. This suits loads with moderate inrush like small motors or lighting."},{"question":"What is the A9N1P03CGN's rated current and voltage?","answer":"Rated current (In) is 3 A. Rated operational voltage (Ue) is 220...240 V AC, 50/60 Hz. Single-pole, single-phase application."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P03CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P03CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}