{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P03CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P03CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P03CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P03CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P03CIN, 1-pole, 3 A, C-curve, 10 kA breaking capacity at 240 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N1P03CIN is a 1-pole miniature circuit breaker from the Acti9 xC60 series, rated 3 A with a C-curve trip characteristic. Breaking capacity is 10 kA Icu at 240 V AC, 15 kA at 12–48 V DC, and 6 kA at 60 V DC, all per IS/IEC 60947-2. The 3 A C-curve is the key selection gate: C-curve trips magnetically at 5–10 x In (here 15–30 A), so it handles moderate inrush from small transformers, lighting ballasts, or control circuits without nuisance trips. The thermal-magnetic trip unit means bimetal for overload, solenoid for short — no electronics to drift. Overvoltage category IV means this breaker is rated for the mains supply entry point — it can handle the transient energy at the service entrance, not just downstream sub-panels. Suitability for isolation per IS/IEC 60947-2 means you can safely use it as a disconnecting means for the downstream circuit during maintenance, provided it's locked off. Wire strip length is 13 mm for top or bottom connection. IP20 finger-safe terminals — fine inside a locked panel, not for wet locations.","metaTitle":"Schneider Electric A9N1P03CIN Acti9 xC60 MCB, 3 A, 1P, C-Cur","metaDescription":"Schneider Electric A9N1P03CIN miniature circuit breaker, 3 A, 1-pole, C-curve, 10 kA breaking capacity per IS/IEC 60947-2. Acti9 xC60 series. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"3 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P03CIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-3a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P03CIN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N1P03CIN and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm position."},{"question":"What is A9N1P03CIN's breaking capacity?","answer":"Breaking capacity is 10 kA Icu at 220–240 V AC, 15 kA at 12–48 V DC, and 6 kA at 60 V DC, all per IS/IEC 60947-2."},{"question":"What standards does A9N1P03CIN comply with?","answer":"It complies with IS/IEC 60947-2, with tropicalisation class 2 per IEC 60068-1 and limitation class 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P03CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P03CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}