{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P04DIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P04DIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P04DIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P04DIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P04DIN, D curve, 4 A, 1 pole, 10 kA breaking capacity at 240 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N1P04DIN is an Acti9 xC60 miniature circuit breaker (MCB) rated at 4 A with a D tripping curve, single-pole construction, and a breaking capacity of 10 kA Icu at 220–240 V AC 50/60 Hz per IS/IEC 60947-2. The 10 kA Icu at 240 V AC is the maximum fault current the breaker can safely interrupt without welding its contacts; for a 4 A branch circuit in a distribution panel, that leaves substantial headroom over typical fault levels in most commercial installations. Clip-on mounting to a standard 35 mm DIN rail and 18 mm width per pole — two 9 mm pitches — so this single-pole breaker occupies one module position in a distribution board. Depth of 77.5 mm and height of 85 mm fit within a standard 125 mm deep enclosure; the white housing with toggle control and ON/OFF local indication makes visual status checks fast during commissioning. Tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible conductors; tightening torque is 2 N·m, and wire stripping length is 13 mm for top or bottom connection. IP20 finger-safe protection is sufficient for enclosed panel use.","metaTitle":"Schneider Electric A9N1P04DIN Acti9 xC60 MCB, D Curve, 4 A,","metaDescription":"Schneider Electric A9N1P04DIN Acti9 xC60 miniature circuit breaker, D curve, 4 A, 1 pole, 10 kA breaking capacity at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"4 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P04DIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-4a-d-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P04DIN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N1P04DIN and how do I get a price?","answer":"The A9N1P04DIN is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9N1P04DIN's listed depth?","answer":"The depth is 77.5 mm, which fits within a standard 125 mm deep enclosure."},{"question":"What is A9N1P04DIN's range?","answer":"It belongs to the Schneider Electric Acti9 range, specifically the xC60 device short name."},{"question":"What compliance documentation does this brand provide for A9N1P04DIN?","answer":"The breaker is certified to IS/IEC 60947-2. The manufacturer typically provides RoHS and REACH declarations; specific compliance documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P04DIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P04DIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}