{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P06BGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P06BGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P06BGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P06BGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit breaker, 1P, 6 A, B curve, 10 kA at 240 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"Schneider Electric A9N1P06BGN is a 1-pole miniature circuit breaker from the Acti9 xC60 series, rated 6 A with a B tripping curve. ## B-curve tripping and thermal-magnetic action The thermal-magnetic trip unit handles sustained overloads via the bimetal strip and short-circuits via the solenoid. The 3...5 x In magnetic threshold means it holds through motor inrush only on the smallest fractional-horsepower motors; for motor circuits a C or D curve is the usual pick. Occupies 2 x 9 mm pitches (18 mm wide) on the DIN rail — standard single-module footprint. Height of 85 mm and depth of 77.5 mm leave enough clearance under a 100 mm deep enclosure lid. Listed as current production. No end-of-life notice or successor code has been issued. This is a standard catalogue item in the Acti9 family, widely specified across South Asia and the Middle East where IS/IEC 60898-1 is the governing standard.","metaTitle":"Schneider A9N1P06BGN Acti9 xC60 MCB, 6A Curve B 1P, 10kA","metaDescription":"Schneider A9N1P06BGN Acti9 xC60 miniature circuit breaker, 6A rated, curve B, 1-pole, 10kA breaking capacity at 240V AC. IS/IEC 60898-1. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P06BGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-6a-b-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P06BGN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCB?","answer":"10,000 A Icn at 240 V AC, 50/60 Hz, conforming to IS/IEC 60898-1. This is the rated short-circuit capacity the breaker can safely interrupt."},{"question":"Where can I buy A9N1P06BGN and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does this breaker carry?","answer":"Certified to IS/IEC 60898-1. The Acti9 xC60 series also carries tropicalisation treatment per IEC 60068-1 (class 2) for humid environments. RoHS and REACH compliance documentation is typically available from the manufacturer's product page for this series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P06BGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P06BGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}