{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P06BIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P06BIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P06BIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P06BIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit breaker, 1P, B curve, 6 A, 10 kA Icu at 240 V AC, clip-on DIN rail, white.","salesMarkdown":"Breaking capacity reaches 10 kA Icu at 220…240 V AC 50/60 Hz per IS/IEC 60947-2, and 15 kA Icu at 12…48 V DC — enough to handle most branch-fault conditions in a standard sub-distribution board. The thermal-magnetic trip unit has a magnetic tripping limit of 4 x In ±20 %. The 77.5 mm depth and 85 mm height fit standard distribution-board enclosures. IP20 finger-safe terminals allow panel-side wiring without additional shrouding. The toggle actuator provides local ON/OFF indication, and the part is suitable for isolation per IS/IEC 60947-2. Rated for 20,000 electrical and 20,000 mechanical cycles. Earth-leakage protection requires a separate block — no integral RCD. Standards compliance includes IS/IEC 60947-2, limitation class 3. The white finish matches the standard Acti9 aesthetic for panel consistency.","metaTitle":"Schneider Electric A9N1P06BIN Acti9 MCB, B Curve 6 A, 10 kA","metaDescription":"Schneider Electric A9N1P06BIN Acti9 miniature circuit breaker, 1P, B curve, 6 A, 10 kA breaking capacity per IS/IEC 60947-2. Active production, clip-on DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P06BIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-6a-b-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P06BIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9N1P06BIN?","answer":"Breaking capacity is 10 kA Icu at 220…240 V AC 50/60 Hz and 15 kA Icu at 12…48 V DC per IS/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P06BIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P06BIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}