{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P06DGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P06DGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P06DGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P06DGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit-breaker, 6 A, D-curve, 1P, 10 kA Icn at 240 V AC, clip-on 35 mm DIN rail, white.","salesMarkdown":"The Schneider Electric A9N1P06DGN is a miniature circuit breaker from the Acti9 xC60 range — a thermal-magnetic MCB built for distribution boards. Its 6 A rated current with a D tripping curve (magnetic trip at 10–14 × In) handles high-inrush loads like small motor starters or lighting ballasts where a B- or C-curve would nuisance-trip on startup. The single-pole unit clips onto a 35 mm DIN rail, occupying 2 × 9 mm pitches (18 mm wide), standard for compact panel layouts. ## Breaking capacity and voltage — what the rating means for fit Rated 10,000 A Icn at 240 V AC, 50/60 Hz, per IS/IEC 60898-1. The operational voltage is 220–240 V AC, single-phase, so it fits a standard line-to-neutral circuit. For anyone checking selectivity with an upstream MCCB, the D-curve's wider magnetic band gives more headroom before the MCB trips on a moderate overcurrent. Clip-on mounting to 35 mm DIN rail, tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible at the bottom connection. Tropicalisation class 2 per IEC 60068-1 means it holds up in high-humidity environments (95% RH at 55 °C).","metaTitle":"Schneider Electric A9N1P06DGN Acti9 xC60 MCB, 6A D-curve, 1P","metaDescription":"Schneider Electric A9N1P06DGN Acti9 xC60 miniature circuit breaker, 6A rated, D-curve, 1 pole, 10kA breaking capacity per IS/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P06DGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-6a-d-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P06DGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N1P06DGN and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to receive current pricing and availability — no stock figures or price lists are published here."},{"question":"What is A9N1P06DGN's listed depth (77.5 mm) on this component line?","answer":"The depth is 77.5 mm, which is the standard depth for a single-module Acti9 xC60 MCB on 35 mm DIN rail — fits most distribution boards without protruding past the enclosure door."},{"question":"What is A9N1P06DGN's listed range (Acti9) on this component line?","answer":"It belongs to the Schneider Electric Acti9 range, specifically the xC60 series of miniature circuit breakers for distribution applications."},{"question":"What compliance documentation does this brand provide for A9N1P06DGN (RoHS, REACH, UL, IEC)?","answer":"The part is certified to IS/IEC 60898-1. The evidence does not list RoHS, REACH, or UL-specific documentation for this order code — check the manufacturer's compliance portal or request a declaration with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P06DGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P06DGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}