{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P10CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P10CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P10CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P10CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N1P10CGN, 1P, 10 A, C-curve, 10 kA breaking capacity, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N1P10CGN is a 1-pole miniature circuit breaker from the Acti9 xC60 family, rated 10 A with a C-curve trip characteristic. That 10 kA Icn breaking capacity at 240 V AC (IS/IEC 60898-1) tells you it can safely interrupt a fault current up to 10,000 A without welding its contacts or rupturing the case; the standard certifies it for final-distribution boards in residential and light commercial panels. The thermal-magnetic trip unit handles overloads (thermal bimetal) and short-circuits (solenoid) in one package — no separate relay needed. The 18 mm width (2 modules) means you can plan fill factor: a 12-way board takes 12 of these single-pole breakers plus a main switch. The toggle actuator gives local ON/OFF indication — no auxiliary contact needed for visual status. Earth-leakage protection requires a separate block (not integrated), so if RCD protection is needed, plan a downstream or adjacent residual-current device.","metaTitle":"Schneider Electric A9N1P10CGN Acti9 xC60 MCB, 10A C-Curve, 1","metaDescription":"Schneider Electric A9N1P10CGN Acti9 xC60 miniature circuit breaker, 10A rated, C-curve, 1-pole, 10kA breaking capacity, IS/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P10CGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-10a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P10CGN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9N1P10CGN?","answer":"The A9N1P10CGN has a rated breaking capacity of 10,000 A Icn at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1. That means it can safely interrupt a fault current up to 10 kA at the rated voltage."},{"question":"What does the C-curve on this MCB mean?","answer":"The C-curve means the magnetic trip threshold is 5 to 10 times the rated current (50–100 A for this 10 A breaker). It is designed for circuits with moderate inrush — lighting banks, small motors, transformers — where a B-curve would nuisance-trip but a D-curve would be too slow for cable protection."},{"question":"Where can I buy the A9N1P10CGN?","answer":"The A9N1P10CGN is sourced and quoted to order through our independent distribution channel. Submit an RFQ for current pricing and availability — we confirm both at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P10CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P10CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}