{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P10CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P10CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P10CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P10CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N1P10CIN, 1-pole, 10 A rated, C-curve, 10 kA breaking capacity at 240 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N1P10CIN is a 1-pole miniature circuit-breaker from the Acti9 xC60 range, rated 10 A with a C-curve trip characteristic. Rated breaking capacity is 10 kA Icu at 220–240 V AC 50/60 Hz per IS/IEC 60947-2, with a 15 kA Icu at 12–48 V DC and 6 kA Icu at 60 V DC. For panels with higher fault levels upstream, verify coordination with the incoming device — the C-curve magnetic trip at 8 x In ±20 % (80 A nominal) clears fast enough to support selective coordination in a properly graded system. The IP20 finger-safe front allows panel-side handling without additional shrouding.","metaTitle":"Schneider Electric A9N1P10CIN Acti9 MCB, 10 A C-Curve, 1P","metaDescription":"Schneider Electric A9N1P10CIN Acti9 miniature circuit-breaker, 10 A rated, C-curve, 1-pole, 10 kA breaking capacity at 240 V AC. IS/IEC 60947-2. Current lifecycle. Available to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P10CIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-10a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P10CIN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N1P10CIN and how do I get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9N1P10CIN's breaking capacity at 240 V AC?","answer":"Rated 10 kA Icu at 220–240 V AC 50/60 Hz per IS/IEC 60947-2, with 15 kA at 12–48 V DC and 6 kA at 60 V DC."},{"question":"What is the C-curve trip threshold on this MCB?","answer":"Magnetic tripping limit is 8 x In ±20 %, so the magnetic trip fires between 64 A and 96 A for the 10 A rated version."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P10CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P10CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}