{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P16DGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P16DGN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P16DGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P16DGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, 1P, 16 A, D curve, 10 kA Icn at 240 V AC, 35 mm DIN rail, clip-on mount.","salesMarkdown":"The Schneider Electric A9N1P16DGN is a 1-pole Acti9 xC60 miniature circuit breaker rated 16 A with a D tripping curve and a 10 kA breaking capacity at 240 V AC. That's the range you want for loads with a high inrush: a 16 A motor drawing 100 A for a few cycles on start won't pop this breaker, but a hard fault will clear it fast. Thermal-magnetic trip technology means the bimetal strip handles the overload curve (slow, heat-based) while the solenoid handles short-circuit (instant, magnetic). The IP20 finger-safe terminals keep accidental contact out during commissioning. ## Panel integration Clip-on mount onto 35 mm DIN rail. Width is 18 mm (2 x 9 mm pitches), so it takes one modular space in the enclosure. Height 85 mm, depth 77.5 mm — fits standard distribution boards without crowding the gland plate. Tightening torque 2 N.m — no special tooling needed.","metaTitle":"Schneider A9N1P16DGN Acti9 xC60 MCB, 16 A, D Curve, 10 kA","metaDescription":"Schneider Electric A9N1P16DGN Acti9 xC60 miniature circuit breaker, 16 A, D curve, 10 kA breaking capacity, 1P, 240 V AC. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P16DGN/miniature-circuit-breaker-mcb-acti9-xc60-1p-16a-d-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P16DGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9N1P16DGN?","answer":"We source the A9N1P16DGN to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the A9N1P16DGN?","answer":"The A9N1P16DGN has a 10 kA Icn breaking capacity at 240 V AC, 50/60 Hz, certified to IS/IEC 60898-1."},{"question":"What does the D curve mean for this breaker?","answer":"The D curve sets magnetic tripping at 10 to 14 times the rated current (160–224 A for the 16 A version), making it suitable for loads with high inrush such as motors and transformers."},{"question":"What compliance standards does the A9N1P16DGN meet?","answer":"The A9N1P16DGN is certified to IS/IEC 60898-1 and has tropicalisation level 2 per IEC 60068-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P16DGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P16DGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}