{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P40CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P40CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P40CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P40CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, 1-pole, 40 A, C-curve, 10 kA Icu at 240 V AC, clip-on for 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N1P40CIN is a 40 A, 1-pole miniature circuit breaker from the Acti9 xC60 range, built to IS/IEC 60947-2. At 12–48 V DC it delivers 15 kA Icu, so it works in DC sub-distribution or control power feeds too. Clip-on mounting to a 35 mm DIN rail, 18 mm wide (2 x 9 mm pitches), 85 mm tall, 77.5 mm deep. That 77.5 mm depth means it sits flush with most standard distribution boards — no extra clearance needed behind the rail. Strip length 13 mm, tighten to 3.5 N·m.","metaTitle":"A9N1P40CIN Acti9 MCB, 40 A, 1P, C-curve, 10 kA","metaDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, 40 A, 1-pole, C-curve, 10 kA breaking capacity at 240 V AC. IS/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P40CIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-40a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P40CIN/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N1P40CIN?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network — no online price or live count is displayed."},{"question":"What is A9N1P40CIN's listed depth?","answer":"77.5 mm, which fits standard distribution board depths without extra rear clearance."},{"question":"What standards does A9N1P40CIN comply with?","answer":"It conforms to IS/IEC 60947-2, with pollution degree 3, overvoltage category IV, and suitability for isolation per that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P40CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P40CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}