{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N1P50CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N1P50CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N1P50CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N1P50CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit-breaker, 1P, 50 A, C curve, 10 kA Icu at 240 V AC, clip-on 35 mm DIN rail, IS/IEC 60947-2.","salesMarkdown":"## Acti9 xC60 50 A MCB — panel-builder commissioning notes The C curve means magnetic tripping occurs at 8 x In (±20 %), so the breaker holds through motor inrush and transformer energisation but clears a hard short fast. For a 50 A circuit, that is a magnetic pickup between roughly 320 A and 480 A — typical for general-purpose distribution feeding mixed resistive and light inductive loads. Breaking capacity is 10 kA Icu at 220…240 V AC (50/60 Hz) per IS/IEC 60947-2, with a 15 kA Icu rating at 12…48 V DC and 6 kA Icu at 60 V DC. The standard certifies the breaker for isolation (suitability for isolation: yes) and assigns it utilisation category A — meaning it is not intended for frequent switching of motor loads but for cable and equipment protection in distribution. The IP20 finger-safe enclosure is adequate for enclosed distribution boards; no washdown rating is claimed. ## Lifecycle and compliance — current production, tender-ready The A9N1P50CIN carries a lifecycle stage of current, per the manufacturer's classification. It remains an active catalogue number within the Acti9 range, fully compliant with IS/IEC 60947-2 and tropicalised to IEC 60068-1 (class 2). For tender submissions requiring a traceable, in-production MCB with a published standard, this part meets the documentation threshold without a substitution note.","metaTitle":"Schneider Electric A9N1P50CIN Acti9 xC60 MCB, 50 A, 1P, C Cu","metaDescription":"Schneider Electric A9N1P50CIN Acti9 xC60 miniature circuit-breaker, 50 A rated current, 1 pole, C curve, 10 kA Icu at 240 V AC. IS/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 12...48 V DC conforming to IS/IEC 60947-2 6 kA Icu at 60 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 12...48 V DC 60 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"15 kA conforming to IS/IEC 60947-2 - 12...48 V DC 6 kA conforming to IS/IEC 60947-2 - 60 V DC 7.5 kA conforming to IS/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N1P50CIN/miniature-circuit-breaker-mcb-acti9-xc60-1p-50a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N1P50CIN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9N1P50CIN and get a price?","answer":"The A9N1P50CIN is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the A9N1P50CIN?","answer":"The breaking capacity is 10 kA Icu at 220…240 V AC 50/60 Hz, 15 kA Icu at 12…48 V DC, and 6 kA Icu at 60 V DC, all conforming to IS/IEC 60947-2."},{"question":"What is the A9N1P50CIN's magnetic trip threshold?","answer":"The magnetic tripping limit is 8 x In ±20 %, so for the 50 A rating the instantaneous trip picks up between approximately 320 A and 480 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N1P50CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N1P50CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}