{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N26500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N26500","canonicalUrl":"https://aoctrl.com/schneider/A9N26500","factsUrl":"https://aoctrl.com/api/mcp/products/A9N26500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iMSU overvoltage release, A9N26500, threshold 255-400V, 230V AC control circuit, 18mm wide, DIN rail mount, EN 50550.","salesMarkdown":"It monitors the control circuit at 230 V AC 50/60 Hz and trips according to a stepped curve: 255-275 V in 3-15 s, 300 V in 1-5 s, 350 V in 0.25-0.75 s, and 400 V in 0.07-0.2 s. That means it catches sustained swells before they damage downstream equipment, while ignoring brief transients that wouldn't harm anything. At 18 mm wide (2 x 9 mm pitches), it occupies a single module slot. Depth is 73.5 mm, height 82.5 mm. Tightening torque is 1 N·m; strip length 9-10 mm. Top-side comb busbar compatible. This part is marked obsolete by the manufacturer. If you're freezing a new design, look at the current Acti9 overvoltage release range; the iMSU form factor and trip characteristics have evolved, so verify the trip curve and DIN footprint against your panel layout. Built to EN 50550, the European standard for power-frequency overvoltage protective devices (POPs). CE marked. The local action indicator gives a visual trip signal, which helps during fault-finding without needing to meter the circuit.","metaTitle":"A9N26500 Acti9 iMSU Overvoltage Release, 255-400V, Obsolete","metaDescription":"Schneider Electric A9N26500 Acti9 iMSU overvoltage release, threshold 255-400V, 230V AC control. Obsolete — sourced to order against RFQ. DIN rail, 18mm wide.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"73.5 mm","Width":"18 mm","Height":"82.5 mm","Coil Voltage":"230 V AC 50/60 Hz","Product Status":"Active","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"50 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Overvoltage release","Ambient Air Temperature Operation":"-25...50 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$108.36 – $114.59","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5af30b796be01acaad9265d1a5ca41a0.pdf","sourceUrl":"https://www.se.com/id/en/product/A9N26500/overvoltage-release-imsu-threshold-255v-to-400v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N26500/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N26500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N26500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}