{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N26583","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N26583","canonicalUrl":"https://aoctrl.com/schneider/A9N26583","factsUrl":"https://aoctrl.com/api/mcp/products/A9N26583","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi xC60 add-on residual current device, 2P, 25 A, Type AC, 300 mA, clip-on DIN rail, 3 modules wide.","salesMarkdown":"The A9N26583: The 25 A rated current (In) sets the maximum continuous load the RCD can carry without derating — sized for a 25 A outgoing circuit, not for a 32 A or 40 A feeder. The 300 mA sensitivity is a time-delay-instantaneous trip for earth leakage, typically used on circuits where nuisance tripping from leakage currents (e.g., long cable runs, surge suppression) is a concern; it is not a 30 mA life-safety threshold. The 2-pole (2P) configuration switches both phase and neutral, and the part occupies 3 modules (9 mm pitches each, 27 mm total width) on the DIN rail. The voltage-independent electromechanical trip coil means the RCD will trip on earth leakage even if the supply voltage is lost — a reliability feature for fault isolation. The bottom tunnel terminals accept 1 to 25 mm² rigid cable (1 to 16 mm² flexible) with a tightening torque of 2 N·m and a strip length of 14 mm. The red indicator on the front face shows tripped status. IP20 rated for the body, IP40 for the modular enclosure — suitable for dry indoor panel environments, not washdown or outdoor use.","metaTitle":"Schneider Electric A9N26583 Vigi xC60 Add-on RCD, 2P 25A AC","metaDescription":"Schneider Electric A9N26583 Vigi xC60 add-on residual current device, 2P, 25A, Type AC, 300 mA sensitivity, clip-on DIN rail mount, active production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74.5 mm","Range":"Acti9","Width":"63 mm","Height":"87 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"3","Network type":"AC","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Red indicator light on the front face","Mounting support":"DIN rail","Pollution degree":"3","Device short name":"Vigi xC60","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"2 N.m bottom","[In] rated current":"25 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","[Ue] rated operational voltage":"230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...240 V conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Electromechanical Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N26583/vigi-xc60-earth-leakage-addon-block-2p-25a-ac-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N26583/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N26583 and how do I get a price?","answer":"The A9N26583 is available to order through independent distribution. Submit an RFQ to receive a current price and lead-time confirmation."},{"question":"What is A9N26583's listed range and depth?","answer":"The A9N26583 belongs to the Acti9 range and has a depth of 74.5 mm, width of 63 mm, and height of 87 mm."},{"question":"What standards does A9N26583 comply with?","answer":"It complies with EN/IEC 61009-1 and EN/IEC 61009-2-1, the standards for residual current operated circuit-breakers with integral overcurrent protection (RCBOs) and for RCDs not incorporating overcurrent protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N26583","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N26583 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}