{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N26596","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N26596","canonicalUrl":"https://aoctrl.com/schneider/A9N26596","factsUrl":"https://aoctrl.com/api/mcp/products/A9N26596","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi xC60 add-on residual current device, 4P, 25 A, Type AC, 100 mA, 400-415 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider A9N26596 is an Acti9 Vigi xC60 add-on residual current device (RCD) — a 4-pole block that clips onto the outgoing side of a compatible MCB to add earth-leakage protection. It's rated 25 A, 400-415 V AC, with a 100 mA sensitivity and Type AC waveform detection. That 100 mA trip threshold means it's sized for general fault protection, not personnel shock prevention (which needs 30 mA or lower). On a 25 A outgoing circuit — lighting, general socket outlets, small distribution — it catches insulation faults and equipment leakage before they escalate. Clip-on mount to DIN rail, 6 x 9 mm module pitches wide (126 mm). It's an add-on block — screws onto the load side of a compatible Acti9 MCB, no extra wiring between them. The tunnel terminals on the bottom accept 1-25 mm² rigid or 1-16 mm² flexible, stripped 14 mm, torqued to 2 N·m. ## Electrical behaviour and standards Voltage-independent electromechanical trip — no auxiliary power needed to detect the fault. Instantaneous response (no intentional time delay), so it's the fast-trip layer in a selective coordination scheme. Rated insulation voltage 500 V AC, impulse withstand 6 kV, and it shrugs off 8/20 µs surge currents up to 250 A without nuisance tripping. Built to EN/IEC 61009-1 and 61009-2-1, pollution degree 3, for 50/60 Hz AC networks. The red indicator on the front shows tripped status at a glance.","metaTitle":"A9N26596 Vigi xC60 Add-on RCD, 4P 25A AC 100mA","metaDescription":"A9N26596 Schneider Acti9 Vigi xC60 add-on RCD, 4P 25A, Type AC, 100 mA, 400-415 V AC. Active production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74.5 mm","Range":"Acti9","Width":"126 mm","Height":"87 mm","Standards":"EN/IEC 61009-2-1 EN/IEC 61009-1","9 Mm Pitches":"6","Network type":"AC","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Red indicator light on the front face","Mounting support":"DIN rail","Pollution degree":"3","Device short name":"Vigi xC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"2 N.m bottom","[In] rated current":"25 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...25 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...16 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","[Ue] rated operational voltage":"400...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 400...415 V conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent Electromechanical","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N26596/vigi-xc60-earth-leakage-addon-block-4p-25a-ac-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N26596/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N26596 and how do I get a price?","answer":"The A9N26596 is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote — availability and current pricing are confirmed at quote time."},{"question":"What is A9N26596's depth?","answer":"The A9N26596 has a depth of 74.5 mm, a width of 126 mm (6 x 9 mm pitches), and a height of 87 mm — fits standard Acti9 modular enclosure spacing on DIN rail."},{"question":"What range is A9N26596 part of?","answer":"It belongs to the Schneider Acti9 range, specifically the Vigi xC60 series of add-on residual current devices."},{"question":"What standards does A9N26596 comply with?","answer":"Compliant with EN/IEC 61009-1 and EN/IEC 61009-2-1, with IP20/IP40 protection ratings per IEC 60529. The manufacturer provides standard compliance documentation on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N26596","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N26596 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}