{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N26612","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N26612","canonicalUrl":"https://aoctrl.com/schneider/A9N26612","factsUrl":"https://aoctrl.com/api/mcp/products/A9N26612","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi xC60 add-on residual current device, A9N26612, 2P, 63 A, 100 mA, Type AC, instantaneous, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9N26612 is a Vigi xC60 add-on residual current device (RCD) from the Acti9 range, designed to bolt onto the outgoing side of a compatible MCB via screw terminals. It is a 2-pole unit rated for 63 A continuous current with a 100 mA earth-leakage sensitivity, Type AC (sinusoidal AC residual currents only). The trip mechanism is electromechanical and voltage-independent — it clears a ground fault even if the phase voltage collapses, which matters for circuits where the neutral reference could be lost. 63 A at 230-240 V AC means this block handles the full current of a 63 A breaker downstream — no derating needed for the RCD itself at that load. The 100 mA sensitivity is less common than 30 mA; it is specified for circuits where nuisance tripping from normal leakage (long cable runs, heater elements, IT equipment) would be a problem, while still providing earth-fault protection. Type AC means it detects only sinusoidal AC residual currents — not pulsed DC or smooth DC — so it is not suitable for circuits with VFDs, UPS outputs, or EV chargers that generate DC fault currents. Clip-on mounting to DIN rail, 4 modules wide (72 mm). The 74.5 mm depth fits standard Acti9 enclosures. Bottom tunnel terminals accept 1 to 35 mm² rigid or 1 to 25 mm² flexible cable; strip length 14 mm, tighten to 3.5 N·m. The red indicator on the front shows tripped status. IP20 on the body, IP40 inside a modular enclosure — fine for dry indoor panels, not for washdown areas.","metaTitle":"Schneider Electric A9N26612 Vigi xC60 RCD Add-on, 2P 63A AC","metaDescription":"Schneider Electric A9N26612 Vigi xC60 add-on residual current device, 2P, 63 A rated current, 100 mA sensitivity, Type AC, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74.5 mm","Range":"Acti9","Width":"72 mm","Height":"87 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"4","Network type":"AC","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Red indicator light on the front face","Mounting support":"DIN rail","Pollution degree":"3","Device short name":"Vigi xC60","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m bottom","[In] rated current":"63 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"100 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","[Ue] rated operational voltage":"230...240 V AC 50/60 Hz conforming to EN/IEC 61009-1 230...240 V conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Electromechanical Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N26612/vigi-xc60-earth-leakage-addon-block-2p-63a-ac-100ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N26612/alternatives.json"},"ai":{"faq":[{"question":"What is the earth leakage sensitivity and type of A9N26612?","answer":"100 mA, Type AC (sinusoidal AC residual currents only), instantaneous trip, voltage-independent electromechanical design."},{"question":"What is the rated current and voltage for A9N26612?","answer":"63 A rated current at 230-240 V AC, 50/60 Hz, 2-pole."},{"question":"What compliance standards does A9N26612 meet?","answer":"Designed to EN/IEC 61009-1 and EN/IEC 61009-2-1. Rated insulation voltage 500 V AC, impulse withstand 6 kV, pollution degree 3."},{"question":"Where can I buy A9N26612?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N26612","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N26612 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}