{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N26645","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N26645","canonicalUrl":"https://aoctrl.com/schneider/A9N26645","factsUrl":"https://aoctrl.com/api/mcp/products/A9N26645","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi xC60 add-on residual current device, 4P, 63 A, 300 mA Type AC, 400-415 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9N26645 is a Vigi xC60 add-on residual current device (RCD) block from the Acti9 range. It clips onto the outgoing side of a compatible MCB or RCBO to add earth-leakage protection where the main breaker lacks it. Rated 63 A continuous, with 300 mA sensitivity and Type AC waveform detection — meaning it trips on sinusoidal AC fault currents, not pulsed or DC components. That makes it a straight choice for general-purpose circuits feeding resistive or lightly inductive loads like heaters, lighting, or small motor starters in a panel. Clip-on mounting on standard DIN rail (35 mm). The 4P block takes up 7 modules of 9 mm pitch — that is 135 mm of rail width. Bottom tunnel terminals accept 1...35 mm² rigid or 1...25 mm² flexible conductors, stripped 14 mm, torqued to 3.5 N·m. The electrical connection to the upstream MCB is via screws, so the assembly stays solid under the vibration you get in a crusher control panel or a conveyor MCC. ## Rated for the line Insulation voltage 500 V AC, impulse withstand 6 kV. Pollution degree 3 — the standard for industrial enclosures where conductive dust or condensation can occur. The electromechanical tripping is voltage-independent, so it clears a fault even if the neutral is lost upstream. Instantaneous trip, no intentional delay. The red indicator on the front face shows a trip condition at a glance — useful when you are troubleshooting a nuisance trip on a mill feed conveyor.","metaTitle":"Schneider Electric A9N26645 Vigi xC60, 63 A 4P 300 mA Type A","metaDescription":"Schneider Electric A9N26645 Vigi xC60 add-on RCD block, 63 A 4P, 300 mA Type AC, 400-415 V AC. Active production. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"74.5 mm","Range":"Acti9","Width":"135 mm","Height":"87 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","9 Mm Pitches":"7","Network type":"AC","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"Red indicator light on the front face","Mounting support":"DIN rail","Pollution degree":"3","Device short name":"Vigi xC60","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"3.5 N.m bottom","[In] rated current":"63 A","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Tunnel type terminal downside for 1 cable(s) 1...35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1...25 mm² flexible with cable end","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","Earth leakage protection type":"Type AC","Electromagnetic compatibility":"8/20 µs impulse withstand, 250 A","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","[Ue] rated operational voltage":"400...415 V AC 50/60 Hz conforming to EN/IEC 61009-1 400...415 V conforming to EN/IEC 61009-2-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Electromechanical Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N26645/vigi-xc60-earth-leakage-addon-block-4p-63a-ac-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N26645/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N26645?","answer":"Submit an RFQ against this order code. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is A9N26645's listed depth (74.5 mm) on this component line?","answer":"The depth is 74.5 mm. That dimension, combined with the 135 mm width (7 x 9 mm pitches) and 87 mm height, defines the envelope for DIN-rail spacing in the panel."},{"question":"What is A9N26645's listed range (Acti9) on this component line?","answer":"It belongs to the Schneider Electric Acti9 range, specifically the Vigi xC60 series of add-on residual current devices."},{"question":"What compliance documentation does this brand provide for A9N26645 (RoHS, REACH, UL, IEC)?","answer":"The A9N26645 is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. IP20 per IEC 60529, IP40 in modular enclosure per IEC 60529. The manufacturer typically provides RoHS and REACH declarations on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N26645","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N26645 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}