{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N2P10BGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N2P10BGN","canonicalUrl":"https://aoctrl.com/schneider/A9N2P10BGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N2P10BGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit-breaker, A9N2P10BGN, 10 A, B-curve, 2P, 10 kA Icn at 240/415 V AC, IS/IEC 60898-1.","salesMarkdown":"## What it is and where it fits The Schneider Electric A9N2P10BGN is a 2-pole miniature circuit-breaker from the Acti9 xC60 series, rated 10 A with a B-curve trip characteristic. It clips onto a 35 mm DIN rail and occupies 4 x 9 mm pitches — 36 mm wide — so it slots into a standard distribution board alongside other Acti9 modules. The thermal-magnetic trip unit handles overloads and short-circuits; the B-curve means magnetic tripping occurs at 3 to 5 times rated current, making it the right choice for resistive or general-purpose loads where inrush is low — lighting circuits, socket outlets, small control transformers. ## Breaking capacity and standards Breaking capacity is 10,000 A Icn at both 240 V and 415 V AC, 50/60 Hz, certified to IS/IEC 60898-1. That 10 kA rating at 415 V is the figure that governs selectivity in a three-phase distribution panel — it tells you the breaker can safely interrupt a fault up to that level without upstream devices needing to clear it. Pollution degree 3 and overvoltage category IV mean it's rated for the harsh electrical environment of a main distribution board, not just a clean sub-panel. ## Integration notes Clip-on mounting to 35 mm DIN rail — no tools needed for installation. Terminals accept up to 25 mm² rigid or 16 mm² flexible; strip length 13 mm. Tightening torque 2 N.m. The white housing with toggle control and ON/OFF indication gives clear visual status. IP20 means it's protected against finger contact but not washdown — keep it inside the enclosure.","metaTitle":"Schneider Electric A9N2P10BGN Acti9 xC60 MCB, 10A B-Curve 2P","metaDescription":"Schneider Electric A9N2P10BGN Acti9 xC60 miniature circuit-breaker, 10 A, B-curve, 2-pole, 10 kA breaking capacity, IS/IEC 60898-1. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N2P10BGN/miniature-circuit-breaker-mcb-acti9-xc60-2p-10a-b-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N2P10BGN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N2P10BGN?","answer":"The A9N2P10BGN has a breaking capacity of 10,000 A Icn at both 240 V and 415 V AC, 50/60 Hz, per IS/IEC 60898-1."},{"question":"Where can I buy A9N2P10BGN?","answer":"The A9N2P10BGN is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the depth of A9N2P10BGN?","answer":"The A9N2P10BGN has a depth of 77.5 mm."},{"question":"What range does A9N2P10BGN belong to?","answer":"The A9N2P10BGN belongs to the Schneider Electric Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N2P10BGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N2P10BGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}