{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N2P20CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N2P20CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N2P20CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N2P20CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N2P20CGN, 2-pole, 20 A rated current, C-curve, 10 kA breaking capacity, clip-on 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric A9N2P20CGN is a 2-pole miniature circuit breaker from the Acti9 xC60 range, rated 20 A with a C-curve trip characteristic. The C-curve means the magnetic trip operates between 5 and 10 times the rated current — so for a 20 A breaker, instantaneous trip occurs between 100 A and 200 A. That makes it a good fit for general-purpose loads like lighting, socket outlets, and small appliances where inrush is moderate. Breaking capacity is 10 kA Icn at both 240 V and 415 V AC, certified to IS/IEC 60898-1. Depth is 77.5 mm, height 85 mm — standard footprint for a 2P MCB in the Acti9 family, so it swaps into an existing board without re-drilling the backplate. The bottom terminals also support a biconnect feature for daisy-chaining or looping out to the next device. The A9N2P20CGN is listed as current-production (active lifecycle stage). No end-of-life notice or last-time-buy date is available for this order code. Certified to IS/IEC 60898-1, the Indian-standard version of the IEC 60898-1 for AC miniature circuit breakers. Pollution degree 3, overvoltage category IV — suitable for main distribution boards where the breaker sees the full utility fault level. Tropicalisation level 2 per IEC 60068-1 means it withstands damp heat — relevant for coastal or high-humidity installations. Relative humidity rating is 95 % at 55 °C. Electrical and mechanical durability both rated at 20,000 cycles — typical for a distribution MCB; not a switching device for frequent motor starts.","metaTitle":"Schneider Electric A9N2P20CGN Acti9 xC60 MCB, 20A, 2P, C-Cur","metaDescription":"Schneider Electric A9N2P20CGN Acti9 xC60 miniature circuit breaker, 20A, 2-pole, C-curve, 10 kA breaking capacity per IS/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"20 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N2P20CGN/miniature-circuit-breaker-mcb-acti9-xc60-2p-20a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N2P20CGN/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N2P20CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N2P20CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}