{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N2P32CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N2P32CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N2P32CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N2P32CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit breaker, A9N2P32CIN, 32 A, 2P, C-curve, 10 kA at 380-415 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"## Breaking capacity & coordination Rated at 10 kA Inc at 380-415 V AC (IS/IEC 60947-2), with a DC rating of 6 kA Icu at 100-125 V DC. That AC figure is typical for a 32 A MCB in a sub-distribution board backed by a larger upstream breaker — the 10 kA withstand covers the prospective fault current in most building-service panels. The DC rating is lower, so if this breaker is used in a DC circuit, the available fault current must not exceed 6 kA. The utilisation category is Category A (no intentional short-time delay), which is standard for MCBs — it trips fast on a short circuit, no selectivity with downstream devices unless they are current-limiting. ## Mounting & connection The 36 mm width (4 x 9 mm pitches) is the standard 2-module footprint for a 2-pole MCB — fits any DIN-rail enclosure. Wire strip length is 13 mm for top or bottom connection. IP20 finger-safe protection on the front face, suitable for enclosed panels only. ## Environmental & isolation Overvoltage category IV (equipment for the origin of the installation, e.g., main distribution boards). Suitability for isolation is confirmed to IS/IEC 60947-2 — the breaker provides a visible isolation gap when switched off.","metaTitle":"Schneider Electric A9N2P32CIN Acti9 xC60 MCB, 32 A, 2P, C-Cu","metaDescription":"Schneider Electric A9N2P32CIN Acti9 xC60 miniature circuit breaker, 32 A rated, 2-pole, C-curve, 10 kA breaking capacity at 380-415 V AC. IS/IEC 60947-2. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"6 kA conforming to IS/IEC 60947-2 - 100...125 V DC 7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N2P32CIN/miniature-circuit-breaker-mcb-acti9-xc60-2p-32a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N2P32CIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of A9N2P32CIN?","answer":"Rated current 32 A, 2 poles, C-curve trip, breaking capacity 10 kA at 380-415 V AC and 6 kA at 100-125 V DC, thermal-magnetic trip unit, suitable for isolation per IS/IEC 60947-2."},{"question":"What compliance documentation does A9N2P32CIN have?","answer":"The breaker is certified to IS/IEC 60947-2. The evidence does not list RoHS, REACH, or UL documentation specifically — these are typically covered by the manufacturer's general compliance declarations for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N2P32CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N2P32CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}