{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N2P63DGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N2P63DGN","canonicalUrl":"https://aoctrl.com/schneider/A9N2P63DGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N2P63DGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, A9N2P63DGN, miniature circuit breaker, 2P, 63 A, D curve, 10 kA Icn at 415 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N2P63DGN is an Acti9 xC60 miniature circuit breaker (MCB) rated for 63 A continuous current, with a D tripping curve that triggers magnetic trip between 10 and 14 times the rated current. The 2-pole configuration protects both phase conductors in a single-phase or split-phase distribution circuit. Breaking capacity is 10 kA Icn at both 240 V and 415 V AC, 50/60 Hz, certified to IS/IEC 60898-1. The thermal-magnetic trip unit combines a bimetal for overload protection and a solenoid for short-circuit — standard MCB architecture, but the D curve's wider magnetic band is what makes this part distinct from the more common C-curve sibling. Clip-on mounting to a 35 mm DIN rail, 4 module pitches wide (36 mm per pole, so 72 mm total width for the 2P unit). Depth is 77.5 mm, height 85 mm — standard for the Acti9 xC60 family, so it fits existing rail layouts without re-spacing. That matters for panels in coastal plants or unairconditioned enclosures.","metaTitle":"Schneider Electric A9N2P63DGN Acti9 xC60 MCB, 63 A, D Curve,","metaDescription":"Schneider Electric A9N2P63DGN Acti9 xC60 miniature circuit breaker, 63 A rated current, D curve, 2-pole, 10 kA breaking capacity at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N2P63DGN/miniature-circuit-breaker-mcb-acti9-xc60-2p-63a-d-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N2P63DGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N2P63DGN and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here."},{"question":"What is the closest alternative to A9N2P63DGN in the Acti9 family?","answer":"The closest peer is the C-curve variant of the same 63 A 2P xC60 (order code A9N2P63C). The only difference is the magnetic trip threshold: C curve trips at 5–10 x In, while the D curve trips at 10–14 x In. Choose D for high-inrush loads like motors and transformers; choose C for general-purpose resistive and moderate-inductive circuits. Footprint, terminals, and breaking capacity are identical."},{"question":"What compliance documentation does this brand provide for A9N2P63DGN?","answer":"The MCB is certified to IS/IEC 60898-1. The Acti9 range typically carries CE marking and meets RoHS requirements, though specific documentation (declaration of conformity, RoHS/REACH reports) should be requested at quote time to match your quality-doc control needs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N2P63DGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N2P63DGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}