{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P01CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P01CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P01CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P01CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 1 A, C-curve, 3-pole, 10 kA breaking capacity per IS/IEC 60898-1, 35 mm DIN rail mount, white.","salesMarkdown":"The Schneider Electric A9N3P01CGN is a 1 A, C-curve, 3-pole miniature circuit breaker from the Acti9 iC60N family. Rated 1 A with a C-curve magnetic trip of 5 to 10 times In, this MCB handles moderate inrush from small motor starters or lighting ballasts without nuisance tripping, while still clearing a hard fault. Breaking capacity is 10 kA at both 240 V AC and 415 V AC, per IS/IEC 60898-1. Snap-on mount to a 35 mm DIN rail, 3-pole wide at 54 mm. The tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible copper, with a tightening torque of 2 N.m. Strip length is 13 mm for top or bottom connection. This fits standard distribution board busbars and outgoing feeder arrangements.","metaTitle":"Schneider Electric A9N3P01CGN iC60N MCB, 1A C-Curve 3P, 10kA","metaDescription":"Schneider Electric A9N3P01CGN iC60N miniature circuit breaker, 1A rated, C-curve, 3-pole, 10kA breaking capacity per IS/IEC 60898-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P01CGN/miniature-circuit-breaker-mcb-acti9-xc60-3p-1a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P01CGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N3P01CGN and how do I get a price?","answer":"The A9N3P01CGN is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll quote it."},{"question":"What is A9N3P01CGN's listed depth?","answer":"The A9N3P01CGN has a depth of 77.5 mm, which is the standard depth for the iC60N range and fits typical distribution board enclosures."},{"question":"What standards does the A9N3P01CGN comply with?","answer":"It complies with IS/IEC 60898-1 for miniature circuit breakers, covering overcurrent protection for household and similar installations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P01CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P01CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}