{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P04CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P04CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P04CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P04CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, 4 A rated current, C-curve, 3-pole, 10 kA breaking capacity, clip-on 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric A9N3P04CGN is a miniature circuit breaker from the Acti9 xC60 range, designed for distribution in AC networks at 50/60 Hz. It is a 3-pole device rated at 4 A with a C-curve (magnetic tripping between 5 and 10 times In), thermal-magnetic trip technology, and a breaking capacity of 10 kA at both 240 V and 415 V AC per IS/IEC 60898-1. The housing is 54 mm wide (6 x 9 mm pitches), 85 mm tall, and 77.5 mm deep, fitting a standard modular enclosure footprint. Wire stripping length is 13 mm for top or bottom connection. ## Durability and auxiliary features Rated for 20,000 electrical and 20,000 mechanical cycles. The toggle switch provides ON/OFF indication, and a contact position indicator shows the true state of the contacts. Earth-leakage protection requires a separate block — this is the MCB only, not an RCBO.","metaTitle":"Schneider Electric A9N3P04CGN Acti9 xC60 MCB, 4A C-Curve, 3P","metaDescription":"Schneider Electric A9N3P04CGN Acti9 xC60 miniature circuit breaker, 4A rated current, C-curve, 3-pole, 10kA breaking capacity per IS/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"4 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P04CGN/miniature-circuit-breaker-mcb-acti9-xc60-3p-4a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P04CGN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N3P04CGN?","answer":"10,000 A Icn at both 240 V and 415 V AC, 50/60 Hz, per IS/IEC 60898-1."},{"question":"What is the rated current and curve of this MCB?","answer":"4 A rated current with a C-curve (magnetic tripping between 5 and 10 times In)."},{"question":"How do I get current pricing and availability for A9N3P04CGN?","answer":"Submit an RFQ through this listing — pricing and availability are confirmed at quote time through our sourcing channels."},{"question":"What compliance documentation does this brand provide for A9N3P04CGN?","answer":"The part is certified to IS/IEC 60898-1. It is rated for pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P04CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P04CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}