{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P06CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P06CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P06CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P06CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N3P06CIN, 6 A, C curve, 3 poles, 10 kA breaking capacity at 415 V AC, IS/IEC 60947-2.","salesMarkdown":"The Schneider Electric A9N3P06CIN is an Acti9 xC60 miniature circuit-breaker rated at 6 A with a C curve, 3 poles, and a breaking capacity of 10 kA Icn at 380–415 V AC and 15 kA Icu at 100–125 V DC, certified to IS/IEC 60947-2. The 15 kA DC rating on the same pole stack is useful for DC auxiliary circuits or battery-backed loads. Thermal-magnetic trip technology means the bimetal handles overloads and the solenoid handles shorts — no electronics to fail or need configuration.","metaTitle":"Schneider Electric A9N3P06CIN Acti9 xC60 MCB, 6 A, C Curve,","metaDescription":"Schneider Electric A9N3P06CIN Acti9 xC60 miniature circuit-breaker, 6 A rated current, C curve, 3 poles, 10 kA breaking capacity at 415 V AC. IS/IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P06CIN/miniature-circuit-breaker-mcb-acti9-xc60-3p-6a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P06CIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9N3P06CIN?","answer":"The A9N3P06CIN has a breaking capacity of 10 kA Icn at 380–415 V AC 50/60 Hz and 15 kA Icu at 100–125 V DC, both conforming to IS/IEC 60947-2."},{"question":"What standards does the A9N3P06CIN comply with?","answer":"It complies with IS/IEC 60947-2, which covers low-voltage switchgear and controlgear for circuit-breakers. It also meets tropicalisation class 2 per IEC 60068-1 and limitation class 3 per IS/IEC 60947-2."},{"question":"How do I get pricing and availability for the A9N3P06CIN?","answer":"The A9N3P06CIN is sourced to order against an RFQ through independent distribution; submit a request for current pricing and confirmed availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P06CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P06CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}