{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P16BIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P16BIN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P16BIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P16BIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N3P16BIN, 3-pole, B-curve, 16 A rated current, 10 kA breaking capacity at 415 V AC, 15 kA at 125 V DC, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N3P16BIN is a 3-pole miniature circuit-breaker from the Acti9 xC60 range, rated at 16 A with a B-curve trip characteristic. The B-curve trips magnetically at 4 x In (±20 %), so a 16 A breaker clears short-circuit faults between roughly 51 A and 77 A instantaneously — suited for resistive or general-purpose loads where inrush is low. The 10 kA breaking capacity at 380–415 V AC (IS/IEC 60947-2) means it safely interrupts fault currents up to that level on a 400 V three-phase supply without upstream cascading. At 100–125 V DC the Icu rises to 15 kA, covering DC-side distribution in telecom or solar combiner boxes. The breaker occupies 6 x 9 mm pitches (54 mm width) on a 35 mm DIN rail, with a depth of 77.5 mm and height of 85 mm. IP20 finger-safe terminals suit enclosed panel mounting.","metaTitle":"Schneider Electric A9N3P16BIN Acti9 xC60 MCB, B-Curve 16 A 3","metaDescription":"Schneider Electric A9N3P16BIN Acti9 xC60 miniature circuit-breaker, 16 A rated current, B-curve, 3 poles, 10 kA breaking capacity at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P16BIN/miniature-circuit-breaker-mcb-acti9-xc60-3p-16a-b-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P16BIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the A9N3P16BIN?","answer":"Rated current 16 A, B-curve (magnetic trip at 4 x In), 3 poles, breaking capacity 10 kA at 380–415 V AC (IS/IEC 60947-2) and 15 kA at 100–125 V DC."},{"question":"How do I get pricing and availability for the A9N3P16BIN?","answer":"Submit an RFQ through the storefront; availability and current pricing are confirmed at quote time."},{"question":"What standards does the A9N3P16BIN comply with?","answer":"It complies with IS/IEC 60947-2, pollution degree 3, overvoltage category IV, and is suitable for isolation per that standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P16BIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P16BIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}