{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P16CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P16CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P16CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P16CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit-breaker, A9N3P16CIN, 16 A, 3P, C-curve, 10 kA at 415 V AC, 15 kA at 125 V DC, clip-on DIN rail.","salesMarkdown":"The A9N3P16CIN is a 16 A, 3-pole miniature circuit-breaker from Schneider Electric's Acti9 iC60N family, built to IS/IEC 60947-2. Breaking capacity is 10 kA Icn at 380–415 V AC and 15 kA Icu at 100–125 V DC. That 10 kA AC figure is the standard for most commercial distribution boards in markets following IEC 60947-2; the DC rating is useful for battery-backed or UPS-coupled panels where the fault current can be higher than a typical AC-only MCB handles. Rated for overvoltage category IV and pollution degree 3, so it's suited for the main incoming position in an industrial panel, not just sub-distribution. The thermal-magnetic trip unit gives you the standard two-stage protection: overload via the bimetal, short-circuit via the solenoid. At 54 mm wide (6 x 9 mm pitches), it occupies three modular spaces. Depth is 77.5 mm, height 85 mm, so it fits flush in a typical distribution board without protruding past the cover. Biconnect terminals allow daisy-chaining without pigtails. Strip length is 13 mm; tightening torque is 2 Nm. IP20 finger-safe protection on the front face. Earth-leakage protection is handled by a separate block (Vigi iC60) that clips onto the same DIN rail alongside — the MCB itself is a thermal-magnetic only, no integral RCD. Certified to IS/IEC 60947-2, which covers the breaking capacity, utilization category A, and limitation class 3 (energy-limiting performance). Suitability for isolation is marked on the device — yes, it can be used as a disconnector under that standard.","metaTitle":"Schneider Electric A9N3P16CIN iC60N MCB, 16 A, 3P, C-Curve,","metaDescription":"Schneider Electric A9N3P16CIN Acti9 iC60N miniature circuit-breaker, 16 A, 3-pole, C-curve, 10 kA at 415 V AC, 15 kA at 125 V DC. IS/IEC 60947-2. Active production. Available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P16CIN/miniature-circuit-breaker-mcb-acti9-xc60-3p-16a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P16CIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N3P16CIN?","answer":"10 kA Icn at 380–415 V AC and 15 kA Icu at 100–125 V DC, both per IS/IEC 60947-2. The AC rating covers standard commercial distribution; the DC rating is higher because DC fault currents in battery circuits can be more sustained."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P16CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P16CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}