{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P32BGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P32BGN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P32BGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P32BGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit-breaker, 32 A, B curve, 3P, 10 kA Icn at 240/415 V AC, IS/IEC 60898-1, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N3P32BGN is a 3-pole miniature circuit breaker from the Acti9 xC60 range, rated at 32 A with a B tripping curve (magnetic trip threshold 3 to 5 x In). ## B curve and thermal-magnetic trip The B curve (3–5 x In) means the magnetic trip reacts between 96 A and 160 A for a 32 A breaker. That suits resistive or lighting loads with low inrush — think heater banks, incandescent or LED lighting strings, general socket circuits. The thermal-magnetic trip unit handles the overload side via a bimetal strip; the magnetic coil clears short-circuits. Clip-on mounting on 35 mm DIN rail. Tightening torque 3.5 N·m. The biconnect bottom terminal allows daisy-chaining without extra links — useful when feeding a downstream load from the same phase. IP20 finger-safe protection; the white housing carries an ON/OFF indicator for local status.","metaTitle":"Schneider Electric A9N3P32BGN Acti9 xC60 MCB, 32 A, B Curve,","metaDescription":"Schneider Electric A9N3P32BGN Acti9 xC60 miniature circuit breaker, 32 A rated current, B curve, 3-pole, 10 kA breaking capacity at 240/415 V AC, IS/IEC 60898-1. Sourced to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P32BGN/miniature-circuit-breaker-mcb-acti9-xc60-3p-32a-b-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P32BGN/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N3P32BGN?","answer":"The A9N3P32BGN is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability."},{"question":"What is A9N3P32BGN's breaking capacity?","answer":"The A9N3P32BGN has a breaking capacity of 10,000 A Icn at both 240 V AC and 415 V AC, 50/60 Hz, conforming to IS/IEC 60898-1."},{"question":"What standards does A9N3P32BGN comply with?","answer":"The A9N3P32BGN complies with IS/IEC 60898-1 and carries a pollution degree of 3 and overvoltage category IV. Tropicalisation class 2 per IEC 60068-1 is also listed."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P32BGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P32BGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}