{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P32DIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P32DIN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P32DIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P32DIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit-breaker, 3P, 32 A, D-curve, 10 kA breaking capacity at 380-415 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"## Panel-fit and breaking capacity The Schneider Electric A9N3P32DIN is a 3-pole miniature circuit breaker from the Acti9 xC60 series, rated 32 A with a D tripping curve. Breaking capacity is 10 kA at 380-415 V AC (IS/IEC 60947-2) and 15 kA at 100-125 V DC, giving adequate fault clearance for most commercial and light industrial panelboards. Clips onto a standard 35 mm DIN rail; the 54 mm width (9 mm pitch × 6) fits a 3-pole slot in any Acti9 distribution board.","metaTitle":"Schneider Electric A9N3P32DIN Acti9 xC60 MCB, D-Curve, 32 A,","metaDescription":"Schneider Electric A9N3P32DIN Acti9 xC60 miniature circuit breaker, D-curve, 32 A, 3-pole, 10 kA breaking capacity at 380-415 V AC. IS/IEC 60947-2, active production. Sourced to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P32DIN/miniature-circuit-breaker-mcb-acti9-xc60-3p-32a-d-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P32DIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N3P32DIN?","answer":"10 kA at 380-415 V AC (Icn per IS/IEC 60947-2) and 15 kA at 100-125 V DC (Icu per the same standard)."},{"question":"What compliance standards does A9N3P32DIN meet?","answer":"It conforms to IS/IEC 60947-2, with limitation class 3, suitability for isolation, pollution degree 3, and overvoltage category IV. Tropicalisation class 2 per IEC 60068-1 covers high-humidity environments."},{"question":"Where can I buy A9N3P32DIN and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P32DIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P32DIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}