{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P50CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P50CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P50CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P50CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60, miniature circuit breaker, 50 A, C curve, 3P, 10 kA Icn at 240/415 V AC, clip-on 35 mm DIN rail, thermal-magnetic trip, white.","salesMarkdown":"The Schneider Electric A9N3P50CGN is a 50 A, 3-pole miniature circuit breaker from the Acti9 xC60 family, built to IS/IEC 60898-1 for AC distribution in residential and light commercial panels. Rated breaking capacity is 10 kA Icn at both 240 V and 415 V AC per IS/IEC 60898-1. That 10 kA figure is the same at both voltage levels, so you don't have to derate the interrupting rating when the breaker is used on a 415 V three-phase feed — it holds the full 10 kA across the rated voltage range of 220–240 V and 380–415 V AC. Overvoltage category IV means it's rated for the main distribution board, not just sub-panels, so it can sit at the service entrance where fault currents are highest. Width is 54 mm (6 x 9 mm pitches), depth 77.5 mm, height 85 mm — standard 3-pole MCB footprint for a DIN-rail enclosure. Designed and tested to IS/IEC 60898-1 for overcurrent protection in household and similar installations. Earth-leakage protection requires a separate block — this is a plain MCB, not an RCBO.","metaTitle":"Schneider Electric A9N3P50CGN Acti9 xC60 MCB, 50 A, C Curve,","metaDescription":"Schneider Electric A9N3P50CGN Acti9 xC60 miniature circuit breaker, 50 A rated, C curve, 3-pole, 10 kA breaking capacity at 240/415 V AC. IS/IEC 60898-1. Active production. Quoted","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P50CGN/miniature-circuit-breaker-mcb-acti9-xc60-3p-50a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P50CGN/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9N3P50CGN and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time, not a stock-count promise."},{"question":"What is the breaking capacity of the A9N3P50CGN?","answer":"10 kA Icn at both 240 V and 415 V AC, 50/60 Hz, per IS/IEC 60898-1. The rating holds across the full voltage range without derating."},{"question":"What does the C curve mean on this breaker?","answer":"Magnetic tripping occurs between 5 and 10 times the rated current (250–500 A for this 50 A unit). That's the standard curve for general-purpose distribution where moderate inrush from motors or transformers is expected — it won't nuisance-trip on startup but clears hard faults fast."},{"question":"What compliance documentation does Schneider provide for the A9N3P50CGN?","answer":"The breaker is certified to IS/IEC 60898-1. Tropicalisation per IEC 60068-1 class 2 is documented. For RoHS, REACH, and UL declarations, the manufacturer's compliance portal holds the current declarations — these are available on request with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P50CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P50CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}