{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N3P50CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N3P50CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N3P50CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N3P50CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 series, A9N3P50CIN miniature circuit-breaker, 3P, 50 A, C curve, 10 kA breaking capacity at 380–415 V AC, clip-on 35 mm DIN rail mount.","salesMarkdown":"The Schneider Electric A9N3P50CIN is a 3-pole Acti9 xC60 miniature circuit-breaker rated 50 A with a C curve magnetic trip — 8 x In ±20 % — meaning it holds through moderate inrush and trips on short-circuit fast enough to protect downstream cable. Breaking capacity is 10 kA Icn at 380–415 V AC 50/60 Hz and 15 kA Icu at 100–125 V DC, both per IS/IEC 60947-2. Clip-on mounting to 35 mm DIN rail, 54 mm wide, 85 mm tall, 77.5 mm deep — fits a standard 6-module pitch on the rail. ## Construction and environment IP20 finger-safe terminals, pollution degree 3 (conductive pollution expected), overvoltage category IV — suitable for main distribution panels where the breaker sees the utility-side surge. Mechanical durability 20 000 cycles, electrical 10 000 cycles at rated load. The A9N3P50CIN carries a current lifecycle stage.","metaTitle":"Schneider Electric A9N3P50CIN Acti9 xC60 MCB, 50 A C Curve,","metaDescription":"Schneider Electric A9N3P50CIN Acti9 xC60 miniature circuit breaker, 50 A rated current, C curve, 10 kA breaking capacity at 400 V AC. IS/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100...125 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 100...125 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 - 100...125 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N3P50CIN/miniature-circuit-breaker-mcb-acti9-xc60-3p-50a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N3P50CIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N3P50CIN?","answer":"10 kA Icn at 380–415 V AC 50/60 Hz and 15 kA Icu at 100–125 V DC, both conforming to IS/IEC 60947-2. The AC rating is typical for distribution sub-boards; the DC rating covers battery or solar circuits."},{"question":"What standard does the A9N3P50CIN comply with?","answer":"IS/IEC 60947-2. It is suitability marked for isolation per that standard. Limitation class 3 per the same standard, meaning it limits let-through energy on short-circuit."},{"question":"Where can I buy the A9N3P50CIN?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N3P50CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N3P50CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}