{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N4P01CIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N4P01CIN","canonicalUrl":"https://aoctrl.com/schneider/A9N4P01CIN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N4P01CIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit-breaker, A9N4P01CIN, 4 poles, 1 A, C curve, 10 kA breaking capacity at 380-415 V AC, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N4P01CIN is a 4-pole miniature circuit-breaker from the Acti9 xC60 family, rated at 1 A with a C-curve trip characteristic. It clips onto a 35 mm DIN rail and is designed for distribution in AC or DC networks at 50/60 Hz. The C curve means magnetic tripping occurs between 5 and 10 times the rated current — here, 8 x In ±20 % — so it handles moderate inrush from small motors or transformers without nuisance trips, while still clearing short circuits fast enough for branch protection. Breaking capacity is 10 kA at 380-415 V AC (IS/IEC 60947-2), and 6 kA at 220-250 V DC — enough for most industrial panel feeders where the upstream transformer or supply can deliver that fault current. Clip-on mounting on a 35 mm DIN rail, 72 mm wide, occupying 8 modules of 9 mm pitch. The tunnel-type terminals accept up to 25 mm² rigid or 16 mm² flexible cable; strip length is 13 mm.","metaTitle":"Schneider Electric A9N4P01CIN Acti9 xC60 MCB, 4P, 1 A, C Cur","metaDescription":"Schneider Electric A9N4P01CIN Acti9 xC60 miniature circuit-breaker, 4 poles, 1 A rated current, C curve, 10 kA breaking capacity at 380-415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10 kA Inc at 380...415 V AC 50/60 Hz conforming to IS/IEC 60947-2 6 kA Icu at 220...250 V DC conforming to IS/IEC 60947-2","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m","Device application":"Distribution","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to IS/IEC 60947-2","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (bottom) 16 mm² flexible Tunnel type terminals (bottom) 25 mm² rigid Biconnect (bottom)","IP degree of protection":"IP20","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IS/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IS/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 220...250 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"7.5 kA conforming to IS/IEC 60947-2 - 380...415 V AC 50/60 Hz 6 kA conforming to IS/IEC 60947-2 - 220...250 V DC","[Uimp] rated impulse withstand voltage":"4 kV conforming to IS/IEC 60947-2","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N4P01CIN/miniature-circuit-breaker-mcb-acti9-xc60-4p-1a-c-curve-10ka-is-iec609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N4P01CIN/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N4P01CIN?","answer":"10 kA at 380-415 V AC (Inc per IS/IEC 60947-2) and 6 kA at 220-250 V DC (Icu per the same standard)."},{"question":"Where can I buy A9N4P01CIN?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9N4P01CIN's depth?","answer":"The depth is 77.5 mm."},{"question":"What standards does A9N4P01CIN comply with?","answer":"It complies with IS/IEC 60947-2. Tropicalisation is class 2 per IEC 60068-1. Pollution degree 3, overvoltage category IV."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N4P01CIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N4P01CIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}