{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N4P63CGN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N4P63CGN","canonicalUrl":"https://aoctrl.com/schneider/A9N4P63CGN","factsUrl":"https://aoctrl.com/api/mcp/products/A9N4P63CGN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xC60 miniature circuit breaker, A9N4P63CGN, 63 A rated current, C-curve, 4 poles, 10 kA breaking capacity per IS/IEC 60898-1, 35 mm DIN rail clip-on.","salesMarkdown":"The A9N4P63CGN is a 63 A rated, C-curve miniature circuit breaker from the Acti9 xC60 series, 4-pole, with a breaking capacity of 10 kA at both 240 V and 415 V AC per IS/IEC 60898-1. The C-curve (magnetic trip 5–10 x In) means it handles moderate inrush — typical for motor starters, lighting banks, or transformer primaries — without nuisance trips, while still clearing short-circuits fast enough for the standard. ## Deployment context The toggle gives clear ON/OFF indication for local isolation.","metaTitle":"Schneider Electric A9N4P63CGN Acti9 xC60 MCB, 63 A C-curve 4","metaDescription":"Schneider Electric A9N4P63CGN Acti9 xC60 miniature circuit breaker, 63 A, C-curve, 4 poles, 10 kA breaking capacity per IS/IEC 60898-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"77.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"85 mm","Standards":"IS/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"XC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to IS/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Pollution degree":"3","Range of product":"Acti9","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1 10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1","Device short name":"xC60","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"13 mm for top or bottom connection","Connections - terminals":"Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-30...70 °C","Comb busbar and distribution block compatibility":"Top: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N4P63CGN/miniature-circuit-breaker-mcb-acti9-xc60-4p-63a-c-curve-10000a-is-iec608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N4P63CGN/alternatives.json"},"ai":{"faq":[{"question":"What is A9N4P63CGN's rated breaking capacity?","answer":"10 kA Icn at both 240 V AC and 415 V AC, 50/60 Hz, conforming to IS/IEC 60898-1 — sufficient for most commercial and light industrial distribution boards."},{"question":"What does the C-curve mean on this MCB?","answer":"The magnetic trip operates between 5 and 10 times the rated current (315–630 A for this 63 A unit), so it tolerates motor and transformer inrush without tripping, yet clears short-circuits fast enough for the standard."},{"question":"Where can I buy A9N4P63CGN?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N4P63CGN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N4P63CGN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}