{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N60717","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N60717","canonicalUrl":"https://aoctrl.com/schneider/A9N60717","factsUrl":"https://aoctrl.com/api/mcp/products/A9N60717","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120 series, A9N60717, miniature circuit-breaker, 80 A, C curve, 4P, 5 kA Icu at 230...400 V AC, thermal-magnetic trip, clip-on 35 mm DIN rail.","salesMarkdown":"The A9N60717 is a Schneider Electric Acti9 C120 miniature circuit-breaker rated 80 A at 40 °C with a C curve and 4 poles (4P). Breaking capacity is 5 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2 — that's the maximum fault current it can safely interrupt at those voltages, which governs its use in distribution panels where available fault current stays under that level. Thermal-magnetic trip technology combines a bimetal for overload protection and a solenoid for short-circuit response. The 4-pole version (4P) protects all four conductors in a three-phase plus neutral system.","metaTitle":"Schneider Electric A9N60717 Acti9 C120 MCB, 80 A, C Curve, 4","metaDescription":"Schneider Electric A9N60717 Acti9 C120 miniature circuit-breaker, 80 A rated current, C curve, 4 poles, 5 kA Icu at 230...400 V AC. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"108 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"12","Control type":"Toggle","Network type":"AC","Product name":"Acti9 C120","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Breaking capacity":"5 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"C120a","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"Power circuit: 3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"80 A at 40 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"Power circuit: 15 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals1 cable(s) 1...50 mm² rigid Tunnel type terminals1 cable(s) 1.5...35 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Provision for padlocking":"Yes","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Handle sealable with cable diameter 0.7mm in OFF or ON position","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"230...400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...80 °C","Ambient air temperature for operation":"-30...70 °C","[Ics] rated service breaking capacity":"5 kA 100 % conforming to EN/IEC 60947-2 - 230...400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$135.61","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9018efb3438f0e1f121a669292058853.pdf","sourceUrl":"https://www.se.com/id/en/product/A9N60717/miniature-circuit-breaker-mcb-acti9-c120a-4p-80a-c-curve-5ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N60717/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N60717?","answer":"The A9N60717 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9N60717?","answer":"The A9N60717 has a breaking capacity of 5 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2."},{"question":"What curve and poles does A9N60717 have?","answer":"The A9N60717 is a C-curve, 4-pole (4P) miniature circuit-breaker with a rated current of 80 A at 40 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N60717","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N60717 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}