{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N60733","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N60733","canonicalUrl":"https://aoctrl.com/schneider/A9N60733","factsUrl":"https://aoctrl.com/api/mcp/products/A9N60733","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120N, A9N60733, miniature circuit breaker, 2P, 80 A, C-curve, 10 kA breaking capacity, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N60733 is an Acti9 C120N miniature circuit breaker (MCB) rated 80 A at 40 °C with a C-curve trip characteristic (magnetic trip at 8 x In ±20 %). That 80 A continuous rating means it carries the full load current of a distribution subfeed or a large commercial load without nuisance tripping — sized for a 3-phase 80 A feeder where you need thermal-magnetic protection in a 2-pole (2P) package. The 10 kA breaking capacity (Icu at 230…400 V AC, per EN/IEC 60947-2) tells you it can safely interrupt a fault current up to 10,000 A at the panelboard, which covers most commercial and light industrial service entrances. The C-curve is the standard choice for general distribution loads — motors, lighting, small transformers — where inrush is moderate and you want coordination downstream of a larger upstream device. The 2-pole footprint takes 6 x 9 mm pitches (54 mm wide), so it occupies two module spaces on the rail. Tunnel-type terminals accept 1…50 mm² rigid or 1.5…35 mm² flexible cable; strip 15 mm and torque to 3.5 N·m. IP20 finger-safe terminals are fine for enclosed panels; keep the front cover on in service. Limitation class 3 (energy-limiting) per that standard means it restricts let-through energy in a fault, which helps with downstream device coordination. The manufacturer provides the usual compliance documentation (declaration of conformity, CE marking) for the Acti9 range; specific RoHS/REACH declarations are available on request through the supply channel.","metaTitle":"Schneider Electric A9N60733 Acti9 C120N MCB, 80 A, 2P, C-Cur","metaDescription":"Schneider Electric A9N60733 Acti9 C120N miniature circuit breaker, 80 A rated current, 2 poles, C-curve, 10 kA breaking capacity per EN/IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"54 mm","Height":"81 mm","Voltage":"230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"80 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"10 kA Icu at 10 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-30 °C","Temperature Storage":"-40...80 °C","Electrical Life Cycles":"5000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-30...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$93.25","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c0fceff3daba9c9e41361b9e019691ed.pdf","sourceUrl":"https://www.se.com/id/en/product/A9N60733/miniature-circuit-breaker-mcb-acti9-c120n-2p-80a-c-curve-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N60733/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N60733","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N60733 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}