{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N60782","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N60782","canonicalUrl":"https://aoctrl.com/schneider/A9N60782","factsUrl":"https://aoctrl.com/api/mcp/products/A9N60782","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120H miniature circuit breaker, A9N60782, 2P, 100 A, C curve, 15 kA Icu at 230-400 V AC, thermal-magnetic trip, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N60782 is an Acti9 C120H miniature circuit breaker rated 100 A at 40 °C with a C curve (magnetic trip at 8 x In ±20 %). The 2-pole configuration protects both phase conductors in a single-phase or split-phase circuit. The thermal-magnetic trip unit combines a bimetal element for overload protection (time-delayed, inversely proportional to current) with a solenoid for short-circuit protection (instantaneous above 800 A for this 100 A unit). The C curve is the standard choice for general distribution loads — lighting, small motors, resistive heaters — where inrush currents are moderate. For highly inductive loads like large transformers or motor starters, a D curve would be more appropriate; for purely resistive loads, a B curve offers tighter protection. Occupies 6 x 9 mm pitches (54 mm width) in the enclosure. Tunnel-type terminals accept 1-50 mm² rigid or 1.5-35 mm² flexible conductors; tighten to 3.5 N·m. Strip 15 mm of insulation.","metaTitle":"Schneider Electric A9N60782 Acti9 C120H MCB, 100 A, 2P, C Cu","metaDescription":"Schneider Electric A9N60782 Acti9 C120H miniature circuit breaker, 100 A rated current, 2 poles, C curve, 15 kA breaking capacity per EN/IEC 60947-2. Current production. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"54 mm","Height":"81 mm","Voltage":"230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"80 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"15 kA Icu at 15 kA Icu at 230...400 V AC 50/60 Hz conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-30 °C","Temperature Storage":"-40...80 °C","Electrical Life Cycles":"5000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-30...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/656fe2392a2dbf22256c35cd3598ff1e.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N60782/miniature-circuit-breaker-mcb-acti9-c120h-2p-100a-c-curve-15ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N60782/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N60782","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N60782 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}