{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N61653","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N61653","canonicalUrl":"https://aoctrl.com/schneider/A9N61653","factsUrl":"https://aoctrl.com/api/mcp/products/A9N61653","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60PV-DC, miniature circuit-breaker, 1 A, C-curve, 2 poles, 800 V DC, breaking capacity 3 kA at 650 V DC.","salesMarkdown":"The Schneider Electric A9N61653 is a C60PV-DC miniature circuit-breaker, 1 A rated current, C-curve, 2 poles, rated for 800 V DC. It's built for DC photovoltaic strings and small commercial/residential DC distribution — the C-curve magnetic trip at 8.5 x In handles moderate inrush from inverters or DC-DC converters without nuisance trips. The 3 kA Icu at 650 V DC (1.5 kA at 800 V DC) is the fault-clearing ceiling; the service breaking capacity Ics is the same 3 kA at 650 V DC, meaning it can reclose after a fault at that level without derating. Rated operational voltage 800 V DC. Rated current 1 A. Rated and marked to EN/IEC 60947-2, utilisation category A (no intentional short-time delay — clears fast). Suitable for isolation per that same standard, so it doubles as a disconnector in the DC circuit. The 1500 cycles electrical durability (L/R = 2 ms) and 20000 cycles mechanical durability give a realistic service life for a PV combiner box that sees only a few operations per year.","metaTitle":"Schneider Electric A9N61653 C60PV-DC MCB, 1 A C-Curve, 2P, 8","metaDescription":"Schneider Electric A9N61653 C60PV-DC MCB, 1 A rated current, C-curve, 2 poles, 800 V DC, 3 kA breaking capacity at 650 V DC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.4 mm","Width":"72 mm","Colour":"White","Height":"132.7 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Voltage Drop":"9200 mV 9200 mOhm 9.2 W 1 A","Mounting mode":"Fixed","Market segment":"Small commercial Residential","lifecycle_stage":"current","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"2","Range of product":"C60","Breaking capacity":"3 kA Icu at 650 V DC 1.5 kA Icu at 800 V DC","Device short name":"C60PV-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m","Compatibility code":"C60PV-DC","[In] rated current":"1 A","Polarity sensitivity":"No (can protect against bi-directional current)","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"1500 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel terminal (downside) 1...25 mm² rigid Tunnel terminal (downside) 1...16 mm² flexible Pre-wired cable (upside)","Magnetic tripping limit":"8.5 x In","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking in OFF position","[Ui] rated insulation voltage":"1000 V DC","[Ue] rated operational voltage":"800 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"1.5 kA 100 % - 800 V DC 3 kA 100 % - 650 V DC","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7f2195afe3c2503d7f2d502596d7a8aa.pdf","sourceUrl":"https://www.se.com/my/en/product/A9N61653/c60pvdc-2p-1a-800-v-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N61653/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N61653?","answer":"Breaking capacity is 3 kA Icu at 650 V DC and 1.5 kA Icu at 800 V DC. Service breaking capacity Ics is the same values (100 %), meaning it can reclose after clearing a fault at those levels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N61653","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N61653 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}