{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N61655","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N61655","canonicalUrl":"https://aoctrl.com/schneider/A9N61655","factsUrl":"https://aoctrl.com/api/mcp/products/A9N61655","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric C60PV-DC miniature circuit breaker, A9N61655, 3 A, C curve, 2 poles, 800 V DC, 3 kA breaking capacity at 650 V DC.","salesMarkdown":"It is designed for DC circuits in small commercial and residential photovoltaic installations, isolating and protecting against overcurrent and short-circuit faults per EN/IEC 60947-2. The 3 A rated current (In) sets the continuous load it can carry without tripping; size it for the string current of your PV array or DC load. Breaking capacity is 3 kA Icu at 650 V DC and 1.5 kA Icu at 800 V DC — the maximum fault current it can safely interrupt at those voltages. Service breaking capacity (Ics) is the same values at 100 % of Icu, meaning it can reclose after a fault at full rating without derating. That matters for coordination in a PV combiner box where fault currents can be high. Polarity insensitive — it protects against bi-directional current, which is essential for DC circuits where current can flow either way (e.g., battery banks or PV strings with reverse-current risk). No need to worry about orientation during installation. Takes up 8 x 9 mm pitches (72 mm wide) on the rail, so plan your DIN rail layout accordingly. Ambient operating range -25…70 °C, storage -40…85 °C, with 95 % RH at 55 °C — fine for outdoor enclosures in most climates.","metaTitle":"Schneider Electric A9N61655 C60PV-DC MCB, 3 A, C Curve, 2P,","metaDescription":"Schneider Electric A9N61655 C60PV-DC miniature circuit breaker, 3 A rated current, C curve, 2 poles, 800 V DC, 3 kA breaking capacity at 650 V DC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"77.4 mm","Width":"72 mm","Colour":"White","Height":"132.7 mm","Standards":"EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC","Voltage Drop":"2980 mV 993.3 mOhm 8.9 W 3 A","Mounting mode":"Fixed","Market segment":"Small commercial Residential","lifecycle_stage":"current","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"2","Range of product":"C60","Breaking capacity":"3 kA Icu at 650 V DC 1.5 kA Icu at 800 V DC","Device short name":"C60PV-DC","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2.5 N.m","Compatibility code":"C60PV-DC","[In] rated current":"3 A","Polarity sensitivity":"No (can protect against bi-directional current)","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"1500 cycles L/R = 2 ms","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel terminal (downside) 1...25 mm² rigid Tunnel terminal (downside) 1...16 mm² flexible Pre-wired cable (upside)","Magnetic tripping limit":"8.5 x In","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking in OFF position","[Ui] rated insulation voltage":"1000 V DC","[Ue] rated operational voltage":"800 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"1.5 kA 100 % - 800 V DC 3 kA 100 % - 650 V DC","[Uimp] rated impulse withstand voltage":"6 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a8777767cb724251efd10dd3a97eb44.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N61655/miniature-circuit-breaker-mcb-acti9-c60pvdc-2p-3a-c-curve-1-5ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N61655/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N61655?","answer":"Breaking capacity is 3 kA Icu at 650 V DC and 1.5 kA Icu at 800 V DC. Service breaking capacity (Ics) is the same at 100 % of Icu."},{"question":"What compliance standards does A9N61655 meet?","answer":"It conforms to EN/IEC 60947-2, Category A, and is suitable for isolation per that standard. Polarity insensitive for bidirectional DC protection."},{"question":"Where can I buy A9N61655 and get current pricing?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N61655","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N61655 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}