{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P52606","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P52606","canonicalUrl":"https://aoctrl.com/schneider/A9P52606","factsUrl":"https://aoctrl.com/api/mcp/products/A9P52606","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40 miniature circuit-breaker, A9P52606, 6 A rated, C-curve, 1P+N, 6 kA Icu at 230 V AC, dual-standard EN/IEC 60898-1 and 60947-2.","salesMarkdown":"The Schneider Electric A9P52606 is an Acti9 iC40 miniature circuit-breaker rated 6 A with a C-curve, 1P+N configuration, and a breaking capacity of 6 kA Icu at 230 V AC (per EN/IEC 60947-2) or 4500 A Icn (per EN/IEC 60898-1). This breaker is dual-certified to EN/IEC 60898-1 (domestic / commercial MCB standard) and EN/IEC 60947-2 (industrial CB standard). The 4500 A Icn under 60898-1 is the rated short-circuit capacity for repeated operation in a residential or light commercial panel. Terminals are tunnel type: accept 1–16 mm² rigid or 1–10 mm² flexible, with a tightening torque of 2 N·m. IP20 rated on the body; IP40 in a modular enclosure.","metaTitle":"Schneider A9P52606 Acti9 iC40 MCB, 6 A C-curve 1P+N, 6 kA","metaDescription":"Schneider Electric A9P52606 Acti9 iC40 miniature circuit-breaker, 6 A rated, C-curve, 1P+N, 6 kA Icu at 230 V AC. Dual-rated to EN/IEC 60898-1 and 60947-2. Current production. Avai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"IMQ KEMA","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"6 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2 4500 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In conforming to EN/IEC 60898-1 8 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 4.5 kA 75 % x Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$48.33","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P52606/miniature-circuit-breaker-mcb-acti9-ic40-1p+n-6a-c-curve-4500a-iec-en-608981-6ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P52606/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9P52606?","answer":"The A9P52606 has a breaking capacity of 6 kA Icu at 230 V AC per EN/IEC 60947-2, and 4500 A Icn at 230 V AC per EN/IEC 60898-1."},{"question":"What is the closest alternative to A9P52606 in the same family?","answer":"Within the Acti9 iC40 range, the closest alternative would be a different current rating (e.g., 10 A or 16 A) or a different curve (B or D). For a pin-compatible drop-in with the same 6 A C-curve 1P+N, the A9P52606 is the standard offering; no exact second-source exists from other brands without checking terminal spacing and DIN-rail pitch."},{"question":"Where can I buy A9P52606?","answer":"The A9P52606 is available to order through our distribution channel. Submit an RFQ for current availability and pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P52606","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P52606 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}