{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P54625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P54625","canonicalUrl":"https://aoctrl.com/schneider/A9P54625","factsUrl":"https://aoctrl.com/api/mcp/products/A9P54625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40N miniature circuit breaker, A9P54625, 1P+N, C-curve, 25 A rated current, 10 kA Icu at 230 V AC, DIN-rail clip-on.","salesMarkdown":"The Schneider Electric A9P54625 is an Acti9 iC40N miniature circuit breaker — a 1P+N, C-curve unit rated at 25 A. The thermal-magnetic trip gives you a C-curve magnetic threshold of 5 to 10 times In (8 x In ±20% per EN/IEC 60947-2), meaning it holds through motor inrush and lighting loads but clears a hard short fast. Breaking capacity is 10 kA Icu at 230 V AC under EN/IEC 60947-2, and 6 kA Icn under EN/IEC 60898-1. For most industrial control panels fed from a 230/400 V transformer, the 10 kA Icu covers the available fault current common on a 100 kVA or smaller supply. ## DIN-rail fit and panel integration Clip-on mounting on a DIN rail, 18 mm wide (2 x 9 mm pitches). The neutral is on the left (fixed position), so when you're laying out a row of these in a distribution board, keep the phase busbar on the right side. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip length is 14 mm, torque to 2 N·m. The A9P54625 is listed as current production. It is the standard Acti9 iC40N 25 A C-curve 1P+N MCB. Dual-certified to EN/IEC 60898-1 (the household-breaker standard) and EN/IEC 60947-2 (the industrial-breaker standard). Pollution degree 3 per EN/IEC 60947-2, so it's rated for conductive environments typical in industrial panels. Quality marks include IMQ, OVE, RCM, and AENOR. Suitability for isolation is confirmed per EN/IEC 60947-2, meaning you can use it as a disconnecting means with the toggle in the OFF position and the contact position indicator showing the state.","metaTitle":"Schneider Electric A9P54625 Acti9 iC40N MCB, 1P+N, C-curve,","metaDescription":"Schneider Electric A9P54625 Acti9 iC40N miniature circuit breaker, 1P+N, 25 A, C-curve, 10 kA Icu at 230 V AC. Dual-standard EN/IEC 60898-1 & 60947-2. DIN-rail mount. Current produ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"IMQ OVE RCM AENOR","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40N","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In conforming to EN/IEC 60898-1 8 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$16.20","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P54625/miniature-circuit-breaker-mcb-acti9-ic40n-1p+n-25a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P54625/alternatives.json"},"ai":{"faq":[{"question":"What is A9P54625's listed depth (74 mm) on this component line?","answer":"The A9P54625 has a depth of 74 mm from the DIN-rail mounting face to the front of the toggle. That's standard for the Acti9 iC40N series and matches the cutout depth of most modular distribution enclosures."},{"question":"What is A9P54625's listed range (Acti9) on this component line?","answer":"The A9P54625 belongs to the Acti9 range, specifically the iC40N series. Acti9 is Schneider Electric's modular DIN-rail distribution platform for residential, commercial, and light industrial applications."},{"question":"What compliance documentation does this brand provide for A9P54625 (RoHS, REACH, UL, IEC)?","answer":"The A9P54625 carries quality labels including IMQ (Italy), OVE (Austria), RCM (Australia/New Zealand), and AENOR (Spain). It is certified to EN/IEC 60898-1 and EN/IEC 60947-2. RoHS and REACH compliance documentation is standard for Schneider Electric Acti9 products, though specific declarations are not listed in this evidence set."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P54625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P54625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}