{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P54710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P54710","canonicalUrl":"https://aoctrl.com/schneider/A9P54710","factsUrl":"https://aoctrl.com/api/mcp/products/A9P54710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40N miniature circuit breaker, A9P54710, 10 A, C-curve, 3P+N, 10 kA Icu at 400 V AC, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9P54710 is an Acti9 iC40N miniature circuit breaker rated 10 A, C-curve, 3P+N, with a 10 kA Icu breaking capacity at 400 V AC per IEC 60947-2. The thermal-magnetic trip unit gives you a C-curve magnetic threshold of 5 to 10 times In (8 x In ±20% per IEC 60947-2), so it handles moderate inrush from small motor loads or lighting ballasts without nuisance tripping, while still clearing a hard fault quickly. It carries dual certification to EN/IEC 60898-1 (the household-and-similar standard, Icn 6000 A at 400 V) and EN/IEC 60947-2 (the industrial standard, Icu 10 kA at 400 V). That dual rating means it qualifies for both residential-distribution boards and industrial control panels — the 10 kA Icu is the number you use for SCCR coordination in an industrial enclosure. The tunnel-type terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible copper, with a wire-strip length of 14 mm and a tightening torque of 2 N·m. Neutral is on the left, poles protected are three. The unit includes a contact-position indicator and a trip indicator for visual state at a glance.","metaTitle":"Schneider Electric A9P54710 Acti9 iC40N MCB, 10 A, C-curve,","metaDescription":"Schneider Electric A9P54710 Acti9 iC40N miniature circuit breaker, 10 A rated, C-curve, 10 kA Icu at 400 V AC, 3P+N, DIN rail mount. Current lifecycle active. Sourced to order agai","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"IMQ OVE AENOR","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In conforming to EN/IEC 60898-1 8 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$137.81","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P54710/miniature-circuit-breaker-mcb-acti9-ic40n-3p+n-10a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P54710/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9P54710?","answer":"This part is sourced to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and availability confirmation at quote time."},{"question":"What is the closest pin-compatible alternative to A9P54710 in this component family?","answer":"Within the Acti9 iC40N family, the key differentiator is the rated current (In) and the curve. The A9P54710 is a 10 A, C-curve, 3P+N variant. A direct alternative would be a different In rating within the same iC40N series, but no single 'closest' pin-compatible substitute exists for this exact In/curve/pole combination without changing the protection characteristics."},{"question":"What compliance documentation does this brand provide for A9P54710?","answer":"The A9P54710 carries quality labels including IMQ, OVE, and AENOR, and is certified to EN/IEC 60898-1 and EN/IEC 60947-2 standards. For specific compliance documentation (RoHS, REACH, CE, UKCA), refer to the manufacturer's product documentation package available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P54710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P54710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}