{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P55625","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P55625","canonicalUrl":"https://aoctrl.com/schneider/A9P55625","factsUrl":"https://aoctrl.com/api/mcp/products/A9P55625","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40H, A9P55625, miniature circuit breaker, 1P+N, 25 A, C curve, 10 kA Icn at 230 V AC, thermal-magnetic, clip-on DIN rail.","salesMarkdown":"The Schneider Electric A9P55625 is an Acti9 iC40H miniature circuit breaker — a 1P+N thermal-magnetic MCB rated 25 A with a C curve, meaning magnetic tripping occurs between 5 and 10 times the rated current (125–250 A). Breaking capacity is 10 000 A Icn at 230 V AC, 50/60 Hz, certified to EN/IEC 60898-1. That 10 kA rating covers most secondary-distribution fault levels in a standard building installation; if your upstream transformer or service entrance can deliver more, you'll need a higher-rated upstream device or a current-limiting MCB with a higher Icn. The toggle gives local ON/OFF plus a trip-indicator flag; isolation suitability is marked on the device. The 18 mm width per module means the 1P+N breaker occupies two 9 mm pitches (18 mm total), so plan your enclosure fill accordingly. Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; strip length is 14 mm, tightening torque 2 N.m. IP20 on the body (finger-safe), IP40 inside the modular enclosure.","metaTitle":"Schneider Electric A9P55625 Acti9 iC40H MCB, 25 A, C Curve,","metaDescription":"Schneider Electric A9P55625 Acti9 iC40H miniature circuit breaker, 25 A rated current, C curve, 10 kA breaking capacity at 230 V AC. Current lifecycle stage, sourced to order. EN/I","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"VDE","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"25 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In conforming to EN/IEC 60898-1","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"400 V AC 50/60 Hz","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/il/en/product/A9P55625/miniature-circuitbreaker-acti9-ic40h-1p+n-25-a-c-curve-10000-a-iec-608981-iec-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P55625/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9P55625?","answer":"10 000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That's the maximum fault current it can safely interrupt under standard test conditions."},{"question":"What is the closest alternative to A9P55625 in the same family?","answer":"Within the Acti9 iC40 range, the key variant is the iC40N (standard breaking capacity, typically 6 kA) versus this iC40H (10 kA). If your fault level is lower, the iC40N saves cost; if you need the full 10 kA, stick with the H suffix. No pin-compatible alternative exists outside the Acti9 family without changing the DIN rail footprint."},{"question":"Where can I buy A9P55625?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P55625","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P55625 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}