{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P55706","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P55706","canonicalUrl":"https://aoctrl.com/schneider/A9P55706","factsUrl":"https://aoctrl.com/api/mcp/products/A9P55706","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40H miniature circuit breaker, A9P55706, 3P+N, C-curve, 6 A rated, 10 kA breaking capacity at 400 V AC, thermal-magnetic trip, DIN-rail mount.","salesMarkdown":"The Schneider Electric A9P55706 is a 3P+N miniature circuit breaker from the Acti9 iC40H series, rated 6 A with a C-curve trip characteristic. It delivers a 10 kA breaking capacity (Icn) at 400 V AC, certified to EN/IEC 60898-1 — that means it safely interrupts a 10 kA fault current on a 400 V line without welding its contacts or cascading damage upstream. The thermal-magnetic trip unit gives it the standard C-curve magnetic threshold of 5 to 10 times In, so it's sized for general-purpose distribution loads where moderate inrush (lighting banks, small motor groups, control transformers) is expected. The 3P+N configuration with neutral on the left and three protected poles means it fits a 4-module width (54 mm, 6 x 9 mm pitches). Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible cable; strip length is 14 mm, torque to 2 N·m. IP20 on the terminals, IP40 on the modular enclosure — fine for a clean indoor distribution board, not for washdown zones.","metaTitle":"Schneider Electric A9P55706 Acti9 iC40H MCB, C-Curve 6 A 3P+","metaDescription":"Schneider Electric A9P55706 Acti9 iC40H miniature circuit breaker, 6 A rated, C-curve, 3P+N, 10 kA breaking capacity at 400 V AC. EN/IEC 60898-1. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3","Breaking capacity":"10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40H","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In conforming to EN/IEC 60898-1","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"7500 A 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","[Uimp] rated impulse withstand voltage":"4 kV"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/il/en/product/A9P55706/miniature-circuitbreaker-acti9-ic40h-3p+n-6-a-c-curve-10000-a-iec-608981-iec-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P55706/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9P55706?","answer":"The A9P55706 has a 10 kA breaking capacity (Icn) at 400 V AC, 50/60 Hz, certified to EN/IEC 60898-1. This is the maximum fault current it can safely interrupt at that voltage."},{"question":"What is the rated current and curve of A9P55706?","answer":"It is rated 6 A with a C-curve trip characteristic (magnetic trip threshold 5 to 10 x In). The C-curve is suited for general distribution loads with moderate inrush, such as lighting circuits or small motor groups."},{"question":"Where can I buy A9P55706?","answer":"The A9P55706 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P55706","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P55706 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}