{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P62706","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P62706","canonicalUrl":"https://aoctrl.com/schneider/A9P62706","factsUrl":"https://aoctrl.com/api/mcp/products/A9P62706","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40 miniature circuit breaker, A9P62706, D curve, 6 A rated current, 3P+N poles, breaking capacity 4500 A Icn / 6 kA Icu, clip-on DIN rail mount.","salesMarkdown":"## Acti9 iC40 MCB, D Curve, 6 A, 3P+N The Schneider Electric A9P62706 is an Acti9 iC40 miniature circuit breaker with a D tripping curve, rated 6 A, 3P+N poles. The D curve's magnetic trip threshold of 10–14 x In (12 x In ±20% per EN/IEC 60947-2) means it tolerates the starting surge of inductive equipment without nuisance tripping — a common requirement in industrial panel builds. ## Breaking Capacity and Standards Compliance Rated breaking capacity is 4500 A Icn at 400 V AC per EN/IEC 60898-1 for general distribution, and 6 kA Icu at 400 V AC per EN/IEC 60947-2 for industrial isolation duty. This dual rating lets the part serve both residential/commercial (60898-1) and industrial (60947-2) installations from the same SKU. Height 85 mm, depth 74 mm. Tunnel terminals accept 1–10 mm² flexible or 1–16 mm² rigid wire; strip length 14 mm, tighten to 2 N.m. Neutral is on the left. IP20 finger-safe on the front, IP40 inside a modular enclosure. The 3P+N configuration with three protected poles and a switched neutral is standard for three-phase distribution boards where the neutral is not overload-protected but is switched with the phases.","metaTitle":"Schneider Electric A9P62706 Acti9 iC40 MCB, D Curve, 6 A, 3P","metaDescription":"Schneider Electric A9P62706 Acti9 iC40 miniature circuit breaker, D curve, 6 A rated current, 3P+N poles. Breaking capacity 4500 A Icn / 6 kA Icu. Clip-on DIN rail mount. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"iC40","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"6 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 4.5 kA 75 % x Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P62706/miniature-circuitbreaker-acti9-ic40-3p+n-6-a-d-curve-4500-a-iec-608981-6-ka-iec-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P62706/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the A9P62706?","answer":"Rated current 6 A, D curve, 3P+N poles. Breaking capacity 4500 A Icn at 400 V AC (EN/IEC 60898-1) and 6 kA Icu at 400 V AC (EN/IEC 60947-2). Insulation voltage 440 V AC. Magnetic trip threshold 10–14 x In."},{"question":"Where can I buy the A9P62706?","answer":"The A9P62706 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the A9P62706's depth?","answer":"The depth is 74 mm. Overall dimensions: 85 mm height, 54 mm width (6 modules at 9 mm pitch), 74 mm depth."},{"question":"What compliance standards does the A9P62706 meet?","answer":"It complies with EN/IEC 60898-1 and EN/IEC 60947-2. Pollution degree 3 per 60947-2. IP20 (front) / IP40 (modular enclosure) per IEC 60529. Suitable for isolation per 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P62706","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P62706 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}