{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P62710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P62710","canonicalUrl":"https://aoctrl.com/schneider/A9P62710","factsUrl":"https://aoctrl.com/api/mcp/products/A9P62710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40, miniature circuit breaker, 10 A, D curve, 3P+N, 4.5 kA Icn / 6 kA Icu, clip-on DIN rail.","salesMarkdown":"The Schneider Electric A9P62710 is an Acti9 iC40 miniature circuit breaker rated at 10 A with a D curve, configured 3P+N. Breaking capacity is 4.5 kA Icn per EN/IEC 60898-1 and 6 kA Icu per EN/IEC 60947-2 at 400 V AC — dual-rated so it fits both residential distribution boards (60898-1) and industrial panel schedules (60947-2) without a separate derating calculation. ## D-curve trip behaviour The D curve's magnetic trip fires between 10 and 14 times In per EN/IEC 60898-1, and at 12 x In ±20 % per EN/IEC 60947-2. That high inrush tolerance is sized for motor circuits, transformer primaries, and welding equipment — loads that draw a short-duration surge well above running current without nuisance tripping. Tightening torque 2 N·m top or bottom. Wire strip length 14 mm. IP20 finger-safe on the front; IP40 inside a modular enclosure. Padlocking device compatible for lockout/tagout. Certified to EN/IEC 60898-1 and EN/IEC 60947-2. Pollution degree 3 per 60947-2. Suitability for isolation marked. Operating altitude 2000 m, relative humidity 95 % at 55 °C. Earth-leakage protection via separate block (not integral).","metaTitle":"Schneider Electric A9P62710 Acti9 iC40 MCB, D Curve, 10 A, 3","metaDescription":"Schneider Electric A9P62710 Acti9 iC40 miniature circuit breaker, 10 A rated current, D curve, 3P+N, 4.5 kA (Icn) / 6 kA (Icu) breaking capacity, current lifecycle stage, available","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","lifecycle_stage":"current","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"iC40","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"4500 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 4.5 kA 75 % x Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P62710/miniature-circuitbreaker-acti9-ic40-3p+n-10-a-d-curve-4500-a-iec-608981-6-ka-iec-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P62710/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9P62710?","answer":"4.5 kA Icn per EN/IEC 60898-1 and 6 kA Icu per EN/IEC 60947-2, both at 400 V AC 50/60 Hz."},{"question":"Where can I buy A9P62710 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request with your target quantity."},{"question":"What is the closest alternative to A9P62710 in the Acti9 family?","answer":"Within the same Acti9 iC40 range, the closest peer would share the D curve and 3P+N poles but differ in rated current (e.g., 16 A or 20 A variants) — the A9P62710 is the 10 A version. No pin-compatible drop-in exists at a different rating; the current rating is the selection parameter."},{"question":"What compliance documentation does Schneider provide for A9P62710?","answer":"The part carries EN/IEC 60898-1 and EN/IEC 60947-2 certification. RoHS and REACH compliance documentation is available on request from the manufacturer or distributor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P62710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P62710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}