{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P64710","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P64710","canonicalUrl":"https://aoctrl.com/schneider/A9P64710","factsUrl":"https://aoctrl.com/api/mcp/products/A9P64710","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40N miniature circuit breaker, A9P64710, 3P+N, 10 A rated, D curve, 10 kA Icu at 400 V AC, DIN rail clip-on.","salesMarkdown":"The A9P64710 is a 3P+N miniature circuit breaker from the Schneider Acti9 iC40N line, rated 10 A with a D tripping curve. The 10 kA Icu at 400 V AC (per EN/IEC 60947-2) tells you it can safely interrupt a fault up to that level without welding contacts or cascading upstream; the 6 kA Icn per EN/IEC 60898-1 is the domestic/light-commercial rating. For a panel builder, the 3P+N configuration protects three phases plus switches the neutral, common in three-phase distribution boards where you want the neutral isolated on the same handle. Clip-on mount to standard DIN rail, 6 module pitches wide (54 mm per). Production status is current per the manufacturer — this part is still in the active catalog. No end-of-life notice on record. If you're holding a legacy board that specified this exact order code, it's still a clean drop-in — no last-time-buy scramble needed. Dual-certified to EN/IEC 60898-1 (domestic MCB standard) and EN/IEC 60947-2 (industrial breaker standard), which means it qualifies for both residential distribution boards and industrial panel schedules. Carries OVE and AENOR quality marks — accepted in Central European and Spanish markets. Pollution degree 3 per 60947-2, so it's rated for conductive environments typical in industrial enclosures.","metaTitle":"Schneider Electric A9P64710 Acti9 iC40N MCB, D Curve, 10 A,","metaDescription":"Schneider Electric A9P64710 Acti9 iC40N miniature circuit breaker, 10 A rated, D curve, 10 kA Icu at 400 V AC. DIN rail mount, 3P+N. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"OVE AENOR","lifecycle_stage":"current","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"10 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P64710/miniature-circuit-breaker-mcb-acti9-ic40n-3p+n-10a-d-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P64710/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to A9P64710 in the Acti9 family?","answer":"Within the Acti9 iC40N range, the closest sibling would be a different current rating or curve code — same 3P+N pole configuration, same DIN-rail footprint, same breaking capacity. The D curve and 10 A rating are the specific fit parameters; a C-curve or higher-current variant would trip differently or require larger conductors."},{"question":"What compliance documentation does A9P64710 carry?","answer":"Certified to EN/IEC 60898-1 and EN/IEC 60947-2, with OVE and AENOR quality labels. Pollution degree 3 per 60947-2. The manufacturer provides a declaration of performance and CE marking; RoHS and REACH compliance is standard for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P64710","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P64710 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}