{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9P64716","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9P64716","canonicalUrl":"https://aoctrl.com/schneider/A9P64716","factsUrl":"https://aoctrl.com/api/mcp/products/A9P64716","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC40N miniature circuit breaker, A9P64716, 3P+N, 16 A rated current, D curve, 10 kA Icu at 400 V AC, thermal-magnetic trip, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9P64716 is a 3P+N miniature circuit breaker from the Acti9 iC40N series, rated 16 A with a D tripping curve. The D curve means the magnetic trip operates at 10 to 14 times In (per EN/IEC 60898-1) or 12 x In ±20 % (per EN/IEC 60947-2) — that wide instantaneous threshold is sized for high-inrush loads like motor starters, transformers, and discharge lighting where the start-up surge would nuisance-trip a B or C curve breaker. The thermal-magnetic trip unit handles the overload protection; the magnetic element clears short-circuits. This breaker carries a dual-rated breaking capacity: 10 kA Icu at 400 V AC per EN/IEC 60947-2 (the industrial standard for performance) and 6000 A Icn at 400 V AC per EN/IEC 60898-1 (the household/ commercial standard). The 6 kA Icn rating is the lower commercial-duty value; the breaker is certified to both standards, so it fits installations that require either. It is also approved for isolation (suitability for isolation per EN/IEC 60947-2) — meaning it doubles as a visible-break disconnect when locked off with a padlocking device. The 3P+N body takes 6 x 9 mm pitches — 54 mm wide total — so it occupies three standard module spaces plus a neutral pole. Tunnel terminals accept 1 to 16 mm² rigid or 1 to 10 mm² flexible; tightening torque is 2 N.m top or bottom. IP20 on the terminals, IP40 inside a modular enclosure — fine for a clean panel, not for washdown zones.","metaTitle":"Schneider Electric A9P64716 Acti9 iC40N MCB, 16 A, D Curve,","metaDescription":"Schneider Electric A9P64716 Acti9 iC40N miniature circuit breaker, 16 A rated current, D curve, 10 kA breaking capacity at 400 V AC. Complies with EN/IEC 60898-1 and 60947-2. Avail","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"74 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC40","Mounting mode":"Clip-on","Quality labels":"AENOR OVE","lifecycle_stage":"current","Local signalling":"ON/OFF indication Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC40N","Network frequency":"50/60 Hz","Poles description":"3P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"16 A","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals top or bottom 1...10 mm² flexible Tunnel type terminals top or bottom 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"10...14 x In conforming to EN/IEC 60898-1 12 x In +/- 20 % conforming to EN/IEC 60947-2","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"6000 A 100 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 7.5 kA 75 % x Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/A9P64716/miniature-circuit-breaker-mcb-acti9-ic40n-3p+n-16a-d-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9P64716/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9P64716?","answer":"The A9P64716 has a breaking capacity of 10 kA Icu at 400 V AC per EN/IEC 60947-2 and 6000 A Icn at 400 V AC per EN/IEC 60898-1."},{"question":"Where can I buy A9P64716?","answer":"The A9P64716 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance standards does A9P64716 meet?","answer":"The A9P64716 complies with EN/IEC 60898-1 and EN/IEC 60947-2, and carries quality labels AENOR and OVE."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9P64716","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9P64716 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}